ZX
A
/ Z
XE
MORLEY-IAS
C
OMMISSIONING
M
ANUAL
Document No. 996-071, Revision:
1
,
Aug 99
Page
21
5.3 Peripherals
•
All panels have the facility to drive various Input and Output devices on the 485 peripheral bus (the left hand
serial port D on all base cards). Select the configure option from Page 1 of the Commissioning menus.
CONFIGURE : Loop 1) 2) 3) 4) 5) [1]
6)Peripherals 7) Sounders 8)Relays 9)PC
•
Press ‘
6’
to select the 'Peripherals' option. The display will present a list of options for you to choose from as
follows: -
CONFIGURE : Peripherals 1)Zones [1]
2)Devices 3)Auto Learn 4)Calibrate
•
The top left hand corner of the display reminds you that you are in configuration mode and shows that it is the
peripheral bus that is being examined. Press the appropriate number to select the required menu option.
5.3.1 Auto Learn
•
This facility saves considerable time and effort when installing a system, or when changing the units connected to
the peripheral bus. It allows the system to learn for itself what devices have been installed on the peripheral bus.
•
Press
3
from the configure menu to select "Auto "Learn". The display will respond with the message :-
Auto Learn finds ALL device addresses
and types on loop 1. Shall I do this ?
•
To proceed with "Auto Learn", press the
YES
key. The system will confirm your command with the message
"Program Running" on the display. It may take up to half a minute to learn a complete loop. Each possible sensor
address is checked to see if any detector is installed at that address. If a detector has been installed, the panel
determines the type of the detector. If more than one detector is located at a single address, or the detector type
code is invalid, a warning message will appear on the display.
•
Do not press any key until the display changes from the “program running” message.
•
Once the system has finished learning, it will respond with a display giving a summary of the detectors found on
the loop. For example.
4-way-SCC 4-way-relay 8-way-input Other
3 2 1 4
•
This display should be checked, against the installation sheets, to ensure that the system has found the correct
number of devices.
•
Pressing any key then restores the display to the normal commissioning menu.
•
The Auto Learn sequence can be used as many times as required and does not affect the text description used
to describe the location of each sensor.
Always verify that the system has found all devices correctly. Use the "Devices" option to
obtain detailed information on the device type and to see the address of each device found
on the loop.