OMMISSIONING
M
ANUAL
Document No. 996-071, Revision:
1
,
Aug 99
Page
11
4.5 Step 5 – Configure Day Mode Operation (If required)
•
Select the DAY MODES option from Page 3 of the Commission Menus and then perform the following.
1. Select “Delayed Mode”, if the sounders and outputs are to be delayed.
2. Select “Sensitivity Mode”, if the detectors are to have different pre-alarm and fire alarm settings during day
/ night.
3. Select “Verification Mode”, if the analogue signals are to be verified before the panel registers a fire alarm.
•
Program the required mode as required.
4.6 Step 6 – Configure Network Options (If required)
•
Select the NETWORK option from Page 3 of the Commission Menus. Press
YES
to step through each item to
inspect the factory default settings and change as required. For example, panel address, number of slave panels,
etc.
4.7 Step 7 – Commence Normal Operation
•
Before finally commencing normal operation, perform the following.
1. Select PASSWORDS from Page 2 of the Commission Menus. Set the number of Level 2 passwords and
define the value of each password.
2. Select PROGRAM INTEGRITY from Page 2 of the Commission Menus. Check and record the program
checksums.
•
Select NORMAL OPERATION from Page 1 of the Commission Menus.
Remember to lock the memory.