OMMISSIONING
M
ANUAL
Document No. 996-071, Revision:
1
,
Aug 99
Page
33
11 Day Mode Option
•
Page 3 of the Commission menu is shown below:
1)Day Modes 2)Setup Options 3)Network [1]
4)Events
•
Press
1
to select the ‘Day Modes’ option from Page 3 of the commission menus.
The DAY MODE option and all sub menu options require the Memory Lock to be open.
11.1 Day Modes
•
The display then shows three possible day mode options:
1)Delayed mode 2)Sensitivity mode
3)Verification mode
•
The panel can be commissioned to automatically invoke different operating modes according to the time of day.
•
Each mode has adjustable start and finishing times. Outside of the designated start and finishing times, the panel
reverts to normal operation. If required, a mode can be set independent of time by setting the start to "00:00" and
finish to "24:00"
•
The operating modes available are summarized in the table below.
Operating
Mode
Description
Delayed mode
During the day/night the alarm signal from detectors is immediately recognized and
identified on the panel display, but no outputs turn on until stage1/stage2 timers have
expired. Call points / Pull Stations override this mode.
Sensitivity mode
Allows smoke and temperature detectors to use different pre alarm and fire alarm
thresholds during the day/night.
Verification
mode
Allows smoke detectors to tolerate transient alarms according to the programmed
verification delay time during either day or night.
Table 7 - Day Mode Options
•
Selecting it from the day mode menu can configure each mode.
NOTE: Only one mode of operation can be selected to be operational at a time.