3.5 Enabling Level 2 or Level 3 Access
•
To enable Level 2 or Level 3 operation, press the SHIFT key. The display will then show:
[Panel ACTIVE Control Keys INHIBITED] [1]
Do you want to enable the control keys?
•
Press the
YES
key and the display will prompt for entry of the password.
[Panel ACTIVE Control Keys INHIBITED] [1]
Please Enter Password
•
Enter the
4-digit Level 2 password
. The display then shows the Main Menu of user options.
[ACTIVE] 1)Commission 2)Test 3)Time [1]
4)Enable 5)Disable 6)Print 7)View
•
If a key has not been pressed for a certain period, the display will revert to the normal Level 1 display showing the
system status message. To re-show the menu display, press the
SHIFT
key.
•
If a key has not been pressed for a specified period of time, (normally 5 minutes – programmable), then Level 2
access will be automatically canceled. It will be necessary to re-enter the password to re-activate Level 2
functions.
•
For detailed information on the Level 2 user options, refer to the User Manual (P/N 996-072).
3.5.1 Selecting the commissioning option
•
To access the commissioning functions in the panel, press
1
to select the commission option.
•
The display will prompt for entry of the Level 3 password. Enter the Level 3 password using the number keys and
then press ENTER.
•
The display will then show the commissioning menu options.
3.6 Overview of Menu Structure
•
The commissioning menu options are presented in three different screens (PAGES). When the commissioning
menu option is selected, the display will show:
PAGE 1
1)CONFIGURE YES)More Options [1]
2)Inspect 3)NORMAL OPERATION
•
To move between the three commissioning screens, press the
YES
key.