ZX
A
/ Z
XE
MORLEY-IAS
C
OMMISSIONING
M
ANUAL
Document No. 996-071, Revision:
1
,
Aug 99
Page
29
6 Inspect Option
•
This option allows the entered commissioning data to be viewed and inspected without the risk of inadvertently
changing an entered setting.
•
The operation and functions available are similar to the CONFIGURE option.
7 Time / Date Option
•
Page 2 of the Commission menu is shown below:
1)Time/Date 2)Program Integrity
3)Power Supplies 4)Passwords
•
The TIME / DATE option allows the various time and date functions to be checked or modified.
•
Press
1
from Page 2 of the commission menus to select the Time and Date option. The display then shows a
menu of functions available, as follows:
CHANGE: 1)Time 2)Date 6)System 7)Crystal
•
Select the required option by pressing the appropriate number using the numeric keys.
7.1 Time / Date
•
These options allow the current date and time to be specified and entered into the panel memory.
•
To change the time or date select the appropriate option (Time =
1
, Date =
2
) and enter the correct values.
The time is in 24-hour format.
On networked systems, the time and date will be automatically set by the master panel.
7.2 System (Clear Memory)
•
This option allows the system configuration memory to be cleared. The operation returns all commissioning data
to factory default settings.
•
To select the option, press
6
and follow the instructions.
WARNING:
This option will completely wipe the configuration memory. All previously entered data will
be lost.