37
MRJ04410
ZERO__________________
Then slowly rotate the ENTRY knob in the reverse (Die
Gap Closed) direction while watching the Valve current
indicator until the Valve current reaches Zero or the Die
Gap indicator moves slightly.
Now turn the ENTRY knob in the original direction until the
motion just stops and the Valve current indicator shows
slightly increasing current. The Die Gap has just reached
its closed position.
Push set. Install a dial indicator to indicate Die Gap position.
Set the dial indicator to Zero.
SPAN__________________
The LCD display has changed to indicate SPAN. “
Figure
1-38
” Span is the maximum Die Gap opening and is set,
using the dial indicator, to the die gap tooling designers
specified opening.
Open the die gap by rotating the ENTRY knob. Continue
until the required die gap has been reached. Press Set.
UNITS and Full stroke______________
Press Set or Cursor Key (downward) at Zero/Span Span.
Cursor moves to the Core Stroke Unit – either % or mm. %
will give a die gap opening percentage reference where
100% equals the distance Stroke. mm will give the die gap
opening directly in mm based upon the SPAN setting.
Select the desired units using the ENTRY Knob and press
Set. The value of Full stroke is set as DCDT / SSI full
stroke length. (ex, ±10V=25.4 mm, Full stroke set to 25.4).
The Stroke will automatically calculate from Zero/Span
setting. Which mean 100%=Stroke (mm) showing die gap
opening reference on any display.
Use the ENTRY KNOB to indicate the Stroke in mm.
Move to Back “
Figure 1-39
” and press set. The Setup Display is now shown.
Figure 1-39 Back
Figure 1-38 Die Gap Span Setting