2 - 5 2 - 5
MELSEC-Q
2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM
(d) The modules shown below cannot be used.
Module Name
Type
MELSECNET/IO network
module
A1SJ71LP21, A1SJ71BR11, A1SJ71QLP21,
A1SJ71QLP21S, A1SJ71QLP21GE, A1SJ71QBR11
MELSECNET (II), /B data link
module
A1SJ71AP21, A1SJ71AR21, A1SJ71AT21B
Ethernet interface module
A1SJ71QE71-B2-S3(-B5-S3),
A1SJ71E71-B2-S3(-B5-S3)
Serial communication module,
computer link module
A1SJ71QC24(N), A1SJ71UC24-R2(-R4/-PRF)
CC-Link master-local module
A1SJ61QBT11, A1SJ61BT11
Modem interface module
A1SJ71CMO-S3
ME-NET interface module
A1SJ71ME81
(e) A dedicated instruction for the next module which was present in the QnA/A
series program instruction cannot be used for the High Performance model
QCPU. Re-writing using FROM/TO instruction is required.
Module Name
Type
High speed counter module
A1SD61, A1SD62, A1SD62D(-S1), A1SD62E
MELSECNET/MINI-S3
A1SJ71PT32-S3, A1SJ71T32-S3
Positioning module
A1SD75P1-S3(P2-S3/P3-S3)
ID module
A1SJ71ID1-R4, A1SJ71ID2-R4
(f) Some system configurations and functions are restricted when writing the
parameter of the "High speed interrupt fixed scan interval" setting.
Refer to the following manual for the restrictions when the parameter of the
"High speed interrupt fixed scan interval" setting has been written.
•
High Performance model QCPU (Q mode) User's Manual
(Function Explanation, Program Fundamentals)
Note that the above restrictions do not apply to the High Performance model
QCPU of serial number "04011" or earlier since it ignores the "High speed
interrupt fixed scan interval" setting.
(2) Software package
GX Developer that can use the functions added to the High Performance model
QCPU changes depending on the function version/serial number of the CPU
module.
Function Version
Serial Number
GX Developer
A
—
Version 4 (SW4D5C-GPPW-E) or later
—
Functions added to "02092"
B
—
Version 6 (SW6D5C-GPPW-E) or later
—
Functions added to "03052"
Version 7 (SW7D5C-GPPW-E) or later
—
Functions added to "04012"
Version 7.10L (SW7D5C-GPPW-E)
or later
Refer to Section 2.3 to confirm the function version and serial number of the High
Performance model QCPU.