App - 45 App - 45
MELSEC-Q
APPENDICES
Special Register List (Continued)
ACPU
Special
Conversion
Special
Register after
Conversion
Special
Register for
Modification
Name
Meaning
Details
Corresponding
CPU
D9002
SD1002
I/O module
verification error
I/O module
verification error
module number
• If I/O modules, of which data are different from data
entered, are detected when the power is turned on,
the first I/O number of the lowest number unit among
the detected units is stored in hexadecimal. (Storing
method is the same as that of SD1000.) To monitor
the number by peripheral devices, perform monitor
operation given in hexadecimal.
(Cleared when all contents of SD1116 to SD1123 are
reset to 0.)
• I/O module verify check is executed also to the
modules of remote I/O terminals.
D9004
SD1004
MINI link errors
Stores setting
status made at
parameters
(modules 1 to 8)
• Error status of the MINI(S3) link detected on loaded
AJ71PT32(S3) is stored.
B15
B8
B7
B0
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1
Bits which correspond to faulty
AJ71PT32(S3) are turned on.
Bits which correspond to the signals of
AJ71PT32(S3), shown below, are
turned on as the signals are turned on.
•
Hardware error (X0/X20)
•
MINI(S3) link error datection (X6/X26)
•
MINI(S3) link communication error
(X7/X27)
to
to
QnA
When the AC power supply module is used, 1 is added
at occurrence of an instantaneous power failure of
within 20ms.
(The value is stored in BIN code.)It is reset when power
is switched from OFF to ON.
When the DC power supply module is used, 1 is added
at occurrence of an instantaneous power failure of
within 10ms.
(The value is stored in BIN code.)It is reset when power
is switched from OFF to ON.
D9005
SD1005
AC DOWN
counter
Number of times for
AC DOWN
When the DC power supply module is used, 1 is added
at occurrence of an instantaneous power failure of
within 1ms.
(The value is stored in BIN code.)It is reset when power
is switched from OFF to ON.
QnA
D9008
SD1008
SD0
Self-diagnostic
error
Self-diagnostic
error number
• When error is found as a result of self-diagnosis, error
number is stored in BIN code.
• When one of F0 to 255 is turned on by OUT F or
SET F , the F number, which has been detected
earliest among the F numbers which have turned on,
is stored in BIN code.
• SD62 can be cleared by RST F or LEDR
instruction. If another F number has been detected,
the clearing of SD62 causes the next number to be
stored in SD62.
D9009
SD1009
SD62
Annunciator
detection
F number at which
external failure has
occurred
• When one of F0 to 255 is turned on by OUT F or
SET F , the F number, which has been detected
earliest among the F numbers which have turned on,
is stored in BIN code.
• SD62 can be cleared by executing RST F or
LEDR instruction or moving INDICATOR RESET
switch on CPU front to ON position. If another F
number has been detected, the clearing of SD62
causes the nest number to be stored in SD62.
D9010
SD1010
Error step
Step number at
which operation
error has occurred.
• When operation error has occurred during execution
of application instruction, the step number, at which
the error has occurred, is stored in BIN code.
Thereafter, each time operation error occurs, the
contents of SD1010 are renewed.