App - 53 App - 53
MELSEC-Q
APPENDICES
Special Register List (Continue)
ACPU
Special
Conversion
Special
Register after
Conversion
Special
Register for
Modification
Name
Meaning
Details
Corresponding
CPU
D9216
SD1216
Stores conditions
for up to numbers
1 to 16
D9217
SD1217
Stores conditions
for up to numbers
17 to 32
D9218
SD1218
Stores conditions
for up to numbers
33 to 48
D9219
SD1219
Local station
error detect
status
Stores conditions
for up to numbers
49 to 64
Stores the local station numbers which are in
error.
SD1216
SD1217
SD1218
SD1219
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
L16 L15 L14 L13 L12 L11
L32 L31 L30 L29 L28 L27
L48 L47 L46 L45 L44 L43
L64 L63 L62 L61 L60 L59
L26
L42
L58
L25
L41
L57
L24
L40
L56
L23
L39
L55
L22
L38
L54
L21
L37
L53
L20
L36
L52
L19
L35
L51
L18
L34
L50
L17
L33
L49
L10 L9
L8
L7
L6
L5
L4
L3
L2
L1
Bit
Device
number
If a local station detects an error, the bit corresponding to
the station number becomes "1".
Example: When station 6 and 12 detect an error, bits 5
and 11 in SD1216 become "1", and when
SD1216 is monitored, its value is "2080
(820H)".
D9220
SD1220
Stores conditions
for up to numbers
1 to 16
D9221
SD1221
Stores conditions
for up to numbers
17 to 32
D9222
SD1222
Stores conditions
for up to numbers
33 to 48
D9223
SD1223
Local station
parameters
non-conforming;
remote I/O
station I/O
allocation error
Stores conditions
for up to numbers
49 to 64
Stores the local station numbers which contain
mismatched parameters or of remote station numbers for
which incorrect I/O assignment has been made.
SD1220
SD1221
SD1222
SD1223
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
L16 L15 L14 L13 L12 L11
L32 L31 L30 L29 L28 L27
L48 L47 L46 L45 L44 L43
L64 L63 L62 L61 L60 L59
L26
L42
L58
L25
L41
L57
L24
L40
L56
L23
L39
L55
L22
L38
L54
L21
L37
L53
L20
L36
L52
L19
L35
L51
L18
L34
L50
L17
L33
L49
L10 L9
L8
L7
L6
L5
L4
L3
L2
L1
Bit
Device
number
If a local station acting as the master station of tier three
detects a parameter error or a remote station contains an
invalid I/O assignment, the bit corresponding to the
station number becomes "1".
Example: When local station 5 and remote I/O station
14 detect an error, bits 4 and 13 in SD1220
become "1" , and when SD1220 is monitored,
its value is "8208 (2010H) " .
D9224
SD1224
Stores conditions
for up to numbers
1 to 16
D9225
SD1225
Stores conditions
for up to numbers
17 to 32
D9226
SD1226
Stores conditions
for up to numbers
33 to 48
D9227
SD1227
Local station
and remote I/O
station initial
communications
underway
Stores conditions
for up to numbers
49 to 64
Stores the local or remote station numbers while they are
communicating the initial data with their relevant master
station.
SD1224
SD1225
SD1226
SD1227
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
L/R
16
L/R
15
L/R
14
L/R
13
L/R
12
L/R
11
L/R
10
L/R
9
L/R
8
L/R
7
L/R
6
L/R
5
L/R
4
L/R
3
L/R
2
L/R
1
L/R
32
L/R
31
L/R
30
L/R
29
L/R
28
L/R
27
L/R
26
L/R
25
L/R
24
L/R
23
L/R
22
L/R
21
L/R
20
L/R
19
L/R
18
L/R
17
L/R
48
L/R
47
L/R
46
L/R
45
L/R
44
L/R
43
L/R
42
L/R
41
L/R
40
L/R
39
L/R
38
L/R
37
L/R
36
L/R
35
L/R
34
L/R
33
L/R
64
L/R
63
L/R
62
L/R
61
L/R
60
L/R
59
L/R
58
L/R
57
L/R
56
L/R
55
L/R
54
L/R
53
L/R
52
L/R
51
L/R
50
L/R
49
Bit
Device
number
The bit corresponding to the station number which is
currently communicating the initial settings becomes "1" .
Example: When stations 23 and 45 are communicating,
bit 6 of SD1225 and bit 12 of SD1226
become "1", and when SD1225 is monitored,
its value is "64 (40H)", and when SD1226 is
monitored, its value is "4096 (1000H)"
D9228
SD1228
Stores conditions
for up to numbers
1 to 16
D9229
SD1229
Stores conditions
for up to numbers
17 to 32
D9230
SD1230
Stores conditions
for up to numbers
33 to 48
D9231
SD1231
Local station
and remote I/O
station error
Stores conditions
for up to numbers
49 to 64
Stores the local or remote station numbers which are in
error.
SD1228
SD1229
SD1230
SD1231
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
L/R
16
L/R
15
L/R
14
L/R
13
L/R
12
L/R
11
L/R
10
L/R
9
L/R
8
L/R
7
L/R
6
L/R
5
L/R
4
L/R
3
L/R
2
L/R
1
L/R
32
L/R
31
L/R
30
L/R
29
L/R
28
L/R
27
L/R
26
L/R
25
L/R
24
L/R
23
L/R
22
L/R
21
L/R
20
L/R
19
L/R
18
L/R
17
L/R
48
L/R
47
L/R
46
L/R
45
L/R
44
L/R
43
L/R
42
L/R
41
L/R
40
L/R
39
L/R
38
L/R
37
L/R
36
L/R
35
L/R
34
L/R
33
L/R
64
L/R
63
L/R
62
L/R
61
L/R
60
L/R
59
L/R
58
L/R
57
L/R
56
L/R
55
L/R
54
L/R
53
L/R
52
L/R
51
L/R
50
L/R
49
Bit
Device
number
The bit corresponding to the station number with the error
becomes "1" .
Example: When local station 3 and remote I/O station
14 have an error, bits 2 and 13 of D9228
become "1", and when SD1228 is monitored,
its value is "8196 (2004H)".
QnA
Содержание QCPU (Q Mode)
Страница 111: ...5 19 5 19 MELSEC Q 5 ASSIGNMENT OF I O NUMBERS MEMO ...
Страница 450: ...App 59 App 59 MELSEC Q APPENDICES MEMO ...