19 - 1 19 - 1
MELSEC-Q
19 STARTING UP THE MULTIPLE PLC SYSTEM
19 STARTING UP THE MULTIPLE PLC SYSTEM
This Chapter explains the standard procedures for starting up the multiple PLC
system.
19.1 Flow-chart for Starting Up the Multiple PLC System
Multiple PLC setting, control PLC setting
and other parameter settings.
Creation of sequence programs
Create parameters and sequence programs for PLC No.1
to No.4. For multiple PLC settings and control PLC
settings, see sections 16.1 and 19.2. For automatic
refresh of device data, see section 16.1.
••••••••••••••••••••
••••••••••••••••••••
••••••••••••••••••••
Start
Clarification of function sharing in multiple
PLC system
Clarify the control and functions executed by each CPU.
Purpose of each device and allocation
To use automatic refresh of PLC share memory,
reserve continuous refresh points.
For automatic refresh of PLC share memory, see
section 16.1.
Selection of module to be used
Select the modules for realizing the functions executed in
the multiple PLC system.
Installation of module
Install the selected module to the main base unit and
expansion base units.
GX Developer startup
Start the GX Developer Version 6 or later.
For the starting method, refer to the GX Developer
operating manual.
••••••••••••••••••••
••••••••••••••••••••
••••••••••••••••••••
1)
1)
1
1
PLC power-ON
Select STOP at the RUN/STOP switch of the QCPU and
turn off the RESET/L.CLR switch and turn on the PLC.
Connection of PC and QCPU (PLC No.1)
Connect the PC from which GX Developer has been
started, and the QCPU with the QCPU of the PLC No.1
using RS-232 cable or USB cable.
Parameter and program writing
Write parameters and sequence programs to the PLC
No.1. For PLC No.2 to No.4, select and write the
applicable CPU according to the connection destination
designation.
PLC No.1 QCPU resetting
Set the RESET/L. CLR switch of the QCPU of the PLC
No.1 in the RESET position.
: For systems with a PC CPU module, install GX Developer Version 7 or later
to the PC CPU module to connect the High Performance QCPU with GX
Developer via the bus.
Refer to the GX Developer Version 7 or later operating manual for details.
••••••••••••••••••••
••••••••••••••••••••
••••••••••••••••••••
••••••••••••••••••••