4 - 22 4 - 22
MELSEC-Q
4 SEQUENCE PROGRAM CONFIGURATION AND EXECUTION
CONDITIONS
2 : Synchronous method
(1) Constant scan time setting
The low speed execution type program is operated under the following conditions as shown
below.
• Constant scan time
: 8ms
• Total scan execution type program time
: 4ms to 5ms
• Execution time of low speed execution type program A : 1ms
• Execution time of low speed execution type program B : 3ms
• END processing/low speed END processing
: 0ms (0 ms is used to simplify the illustration)
0
8
16
END
processing
24
32 (ms)
1ms
4.5ms
END
processing
4ms
END
processing
4ms
5ms
Low speed scan time
Scan execution type program
Low speed execution type program A
Low speed execution type program B
END
processing
4ms
Constant scan wait time
0.5ms
2.5ms
Low speed END
processing execution
0.5ms
3ms
1ms
2.5ms
0.5ms
Low speed END
processing execution
0.5ms
3.5ms
Low speed scan time
(13ms)
(15.5ms)
(2) Low speed program execution time setting
The low speed execution type program is operated under the following conditions as shown
below.
• Low speed program execution time
: 3ms
• Total scan execution type program time
: 4ms to 5ms
• Execution time of low speed execution type program A : 1ms
• Execution time of low speed execution type program B : 3ms
• END processing
: 0ms (0 ms is used to simplify the illustration)
0
END
processing
END
processing
16.5
END
processing
23.5
END
processing
29.5
END
processing
(ms)
4ms
1ms
2ms
4.5ms
1ms
4ms
2ms
Low speed scan time
(12ms)
Low speed scan time
(12.5ms)
Low speed END
processing execution
Scan execution type program
Low speed execution type program A
Low speed execution type program B
4
11.5
1ms
1ms
1ms
Low speed END
processing execution
5ms
2ms
4ms