App - 57 App - 57
MELSEC-Q
APPENDICES
Special Register List (Continue)
(14) For redundant systems (Other system CPU information 1) for Q4AR only
SD1600 to SD1659 is only valid during the back up mode for redundant systems, and refresh
cannot be done when in the separate mode. When a standalone system SD1600 to SD1699
are all 0.
Number
Name
Meaning
Explanation
Set by
(When set)
Corresponding
ACPU
SD
2
Corresponding
CPU
SD1600
Diagnosis error
Diagnosis error
No.
• Stores as BIN code the error No. of the error that occurred
during the other system CPU diagnosis.
• Stores the latest error currently occurring.
S (Each
END)
New
SD1601
SD1602
SD1603
Diagnosis error
occurrence
time
Diagnosis error
occurrence time
• SD1600 stores the updated date and time.
• Stores each of the BCD two digits.
• Refer to SD1 to SD3 for the storage status.
(SD1
SD1601, SD2
SD1602, SD3
SD1603)
S (Each
END)
New
SD1604
Error
information
classification
Error
information
classification
• Stores the error comment information/individual information
classification code.
• Refer to SD4 for the storage status.
S (Each
END)
New
SD1605
SD1606
SD1607
SD1608
SD1609
SD1610
SD1611
SD1612
SD1613
SD1614
SD1615
Error common
information
Error common
information
• Stores the common information for the error code.
• Refer to SD5 to SD15 for the storage status.
(SD5
SD1605, SD6
SD1606, SD7
SD1607,
SD8
SD1608, SD9
SD1609, SD10
SD1610,
SD11
SD1611, SD12
SD1612, SD13
SD1613,
SD14
SD1614, SD15
SD1615)
S (Each
END)
New
SD1616
SD1617
SD1618
SD1619
SD1620
SD1621
SD1622
SD1623
SD1624
SD1625
SD1626
Error individual
information
Error individual
information
• Stores the individual information for the error code Refer to
SD16 to SD26 for the storage status.
(SD16
SD1616, SD17
SD1617, SD18
SD1618,
SD19
SD1619, SD20
SD1620, SD21
SD1621,
SD22
SD1622, SD23
SD1623, SD24
SD1624,
SD25
SD1625, SD26
SD1626)
S (Each
END)
New
SD1650
Switch status
CPU switch
status
• Stores the CPU switch status.
• Refer to SD200 for the storage status. (SD1650
SD200)
S (Each
END)
New
SD1651
LED status
CPU-LED status
• Stores the CPU's LED status.
• Shows 0 when turned off, 1 when turned on, and 2 when
flicking.
• Refer to SD201 for the storage status. (SD1651
SD201)
S (Each
END)
New
SD1653
CPU operation
status
CPU operation
status
• Stores the CPU operation status. Refer to SD203 for the
storage status. (SD1653
SD203)
S (Each
END)
New
Q4AR
1 Stores other system CPU self-diagnostic information and system information.
2 Shows the special register (SD
) for the host system CPU.
(15) For redundant systems (Trucking) for Q4AR only
SD1700 to SD1799 is valid only for redundant systems. These are all 0 for standalone
systems.
Number
Name
Meaning
Explanation
Set by
(When set)
Corresponding
ACPU
SD
2
Corresponding
CPU
SD1700
Trucking error
detection count
Trucking error
detection count
• Make it the trucking error det1.
Error
occurrence
New
Q4AR
2 Shows the special register (SD
) for the host system CPU.