14.2.3 Limitations when mounting AnS Series corresponding I/O modules and special
function modules
(1) Compatible I/O modules and special function modules
AnS Series corresponding I/O modules and special function modules (compact
types) can be used with the High Performance model QCPU.
(2) Control PLCs
The AnS Series corresponding I/O modules or special function module can be
controlled by only one PLC (control PLC) of the PLCs No.1 to No.4 when
configuring a multiple PLC system. For example.
If the control PLC is set up as the PLC No.2 as shown in the illustration below,
every slot's control PLC on which I/O modules and special function modules
compatible with the AnS Series are mounted are set as the PLC No.2.
The "PARAMETER ERROR (error code: 3009)" occurs even if only one AnS
Series corresponding I/O module or special function module is set up, the
multiple PLC system will not be started up.
Power
supply
PLC
1
PLC
2
PLC
3
PLC
4
Module
1
Module
1
Module
2
Module
2
Module
3
Module
4
Module
4
Module
4
Module
4
AnS
Module
2
AnS
Module
2
AnS
Module
2
AnS
Module
2
AnS
Module
2
AnS
Module
2
AnS
Module
2
AnS
Module
2
AnS
Module
2
AnS
Module
2
AnS
Module
2
AnS
Module
2
AnS
Module
2
Q312B
QA1S68B
QA1S68B
Control PLCs can be set for each slot
Same PLC set as the control PLC
Module No.
Power
supply
Power
supply
The Module No. shown in the illustration represents the
following:
PLC 1 to 4
: CPU's PLC number
Modules 1 to 4 : Control PLC's PLC number