9 - 1 9 - 1
MELSEC-Q
9 PARAMETER LIST
9
9 PARAMETER LIST
There are two types of parameters used in High Performance model QCPU's
procedures: "PLC parameters" that are used when operating a PLC and "network
parameters" that are used when connecting to the MELSECNET/H or CC-Link system.
The following items required for configuring multiple PLC systems onto PLC
parameters in function version B High Performance model QCPUs have also been
added. (See Section 14.2.6)
• Multiple PLC setup
• Control PLC setup (I/O allocation)
This chapter shows a list of PLC parameters and network parameters used for
GX Developer.
For details on each setting item, refer to the section or manual indicated.
For GX Developer setting procedures, refer to the GX Developer Operating Manual.
The parameters written from the GX Developer will be validated within the QCPU in
the following cases:
• When the power supply to the PLC is switched on.
• When the CPU module is reset.
• When the CPU module changes from STOP to RUN.
However, the PLC parameter's I/O assignment switch settings and the network
parameters will be transmitted from the High Performance model QCPU to a specified
intelligent function module in the following cases, and will be validated within the
intelligent function module.
• When the power supply to the PLC is switched on.
• When the CPU module is reset.
The PLC parameter's I/O assignment switch settings and the network parameters will
not be transmitted from the High Performance model QCPU to a specified intelligent
function module when the High Performance model QCPU is changed from STOP to
RUN.
Switch the power supply to the PLC on once again (ON
OFF ON) or reset the
High Performance model QCPU when the PLC parameter's I/O assignment switch
settings and the network parameters have been amended.
If the High Performance model QCPU is changed from STOP to RUN after PLC
parameter change without this procedure, a PARAMETER ERROR (error code: 3000)
is caused.
POINT
If the PLC parameter's I/O assignment switch settings and the network parameters
are changed, switch the power supply to the PLC on once again (ON OFF
ON) or reset the High Performance model QCPU.
Otherwise, the new PLC parameter's I/O assignment switch settings and network
parameters are not validated.