3. CC-LINK COMMUNICATION FUNCTIONS
(2) Reading the parameter
Read parameter No. PA01 "Control mode" of the servo amplifier of station 2 to D1.
Data No.
Description
H8200 Parameter
group
selection
H2024
Parameter No. PA04 setting (hexadecimal)
The answer code at instruction code execution is set to D9.
Reads remote input of buffer memory
(RX20 to RX5F) to M200 to M263.
Outputs M0 for normal reply.
Turns on instruction code execution
demand (RY29).
Reads RW
R7
of buffer memory to D1
when answer code is normal reply.
Turns off instruction code execution
demand (RY29) and proceeds to the
next when instruction code execution
completion (RX29) turns on.
Writes parameter No.PA04 read (H0204)
to RW
W6
.
Turn off instruction code execution
demand (RY29).
Writes M100 to M163 to remote output
(RY20 to RY5F) of buffer memory.
Writes parameter group No. write
(H8200) to RW
W6
and parameter group
PA (K0) to RW
W7
.