3 - 30
3. CC-LINK COMMUNICATION FUNCTIONS
Code No.
Item
Writing data (RWwn+3) contents
(PLC Servo amplifier)
9001h
to
90FFh
Dwell data EEP-ROM command of point table
Writes the dwell data of point table No. 1 to 255 to EEP-
ROM. Written to EEP-ROM, these values are held if
power is switched off.
The decimal value converted from the 2 lower digits of
the code No. corresponds to the point table No.
Convert the values into hexadecimal before making
setting.
9101h
to
91FFh
Auxiliary function data EEP-ROM command of point
table
Writes the auxiliary function data of point table No. 1 to
255 to EEP-ROM. Written to EEP-ROM, these values
are held if power is switched off.
The decimal value converted from the 2 lower digits of
the code No. corresponds to the point table No.
Convert the values into hexadecimal before making
setting.
3.5.5 Answer codes (RWrn+2)
If any of the monitor codes, instruction codes, position command data/point table Nos., speed command
data/point table Nos. set to the remote register is outside the setting range, the corresponding error code is set
to Answer code (RWwn+2). "0000" is set if they are normal.
Error related to Monitor code 1/Monitor code 2
Error related to Instruction code/Writing data
Error related to Position instruction data/Point table No.
Error related to Speed instruction data/Point table No.
Code No.
Error
Details
0
Normal answer
Instruction was completed normally.
1
Code error
The monitor code not in the specifications was set.
Read/write of the point table of No. 255 or later was set.
2
Parameter point table
selection error
The parameter No. disabled for reference was set.
3
Write range error
An attempt was made to write the parameter or point table data outside
the setting range.