15 - 15
15. COMMUNICATION FUNCTION
(8) Point table/acceleration time constant (Command [C][7])
Command
Data No.
Description
Setting range
Frame length
[C][7]
[0][1] to [F][F] Acceleration time constant write
The decimal equivalent of the data No. value
(hexadecimal) corresponds to the Point table No.
0 to 20000
8
(9) Point table/deceleration time constant (Command [C][8])
Command
Data No.
Description
Setting range
Frame length
[C][8]
[0][1] to [F][F] Deceleration time constant write
The decimal equivalent of the data No. value
(hexadecimal) corresponds to the Point table No.
0 to 20000
8
(10) Point table/dwell (Command [C][A])
Command
Data No.
Description
Setting range
Frame length
[C][A]
[0][1] to [F][F] Dwell write
The decimal equivalent of the data No. value
(hexadecimal) corresponds to the Point table No.
0 to 20000
8
(11) Point table/auxiliary function (Command [C][B])
Command
Data No.
Description
Setting range
Frame length
[C][B]
[0][1] to [F][F] Auxiliary function write
The decimal equivalent of the data No. value
(hexadecimal) corresponds to the Point table No.
0 to 3
8
(12) External input signal disable (Command [9][0])
Command
Data No.
Description
Setting range
Frame length
[9][0]
[0][0]
Turns off the input devices, external analog input signals
and pulse train inputs with the exception of EMG, LSP and
LSN, independently of the external ON/OFF statuses.
1EA5 4
[9][0]
[0][3]
Changes the output devices (DO) into the value of
command [8][B] or command [A][0] data No. [0][1].
1EA5 4
[9][0]
[1][0]
Enables the disabled input devices (DI), external analog
input signals and pulse train inputs with the exception of
EMG, LSP and LSN.
1EA5 4
[9][0]
[1][3]
Enables the disabled output devices (DO).
1EA5
4
(13) Operation mode selection (Command [8][B])
Command
Data No.
Description
Setting Range
Frame Length
[8] [B]
[0] [0]
Operation mode switching
0000: Test operation mode cancel
0001: JOG operation
0002: Positioning operation
0003: Motorless operation
0004: Output signal (DO) forced output
0005: Single-step feed
0000 to 0005
4
Содержание MELSERVO MR-J3-xT
Страница 22: ...8 MEMO ...
Страница 156: ...4 46 4 SIGNALS AND WIRING MEMO ...
Страница 276: ...7 26 7 MR Configurator MEMO ...
Страница 324: ...10 16 10 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 418: ...14 66 14 OPTIONS AND AUXILIARY EQUIPMENT MEMO ...