Setting brand comparison targets (Targeted functions from F21 to F26)
Note:
-
The ON/OFF status for each output may difer depending on selection. If an
inappropriate mode is selected, the ON/OFF status may be incorrect, leading to
malfunction of peripheral instruments.
-
The set points of S1, S2, S3, and S4 are shared between 4-steps check mode 1 and
4-steps check mode 2.
-
Output for each comparison is synchronized with A/D sampling.
11.6.1
Comparison targets for S1, S2, S3 and S4 in check mode
The comparison targets for the check mode can be set individually for S1, S2, S3 and S4 to
[Display interlock], [NET WEIGHT] or[GROSS WEIGHT]. Select in Function mode (F-21).
The default is [Display interlock] for S1, S2, S3 and S4.
11.6.2
S1, S2, S3 and S4 comparison operation
Operation of comparators S0, S1, S2, S3, and S4 in this mode are shown below.
S1 output is ON provided that the comparison target value is less than the S1 set value.
S2 output turns ON when S1 set point ≤ comparison value < S2 set point.
S0 output turns ON when S2 set point ≤ comparison value < S3 set point.
S3 output turns ON when S3 set point ≤ comparison value < S4 set point.
S4 output turns ON when S4 set point ≤ comparison value < S4 set point.
S3 output ON
S3 output OFF
comparison
value (smaller)
comparison
value (larger)
S1 set value
S3 set value
S4 output ON
S4 output OFF
S0 output ON
S0 output OFF
S2 output ON
S2 output OFF
S1 output ON
S1 output OFF
S4 set value
S2 set value
11.6.3
Hysteresis in check mode
S1, S2, S3 and S4 can be set to prevent output relay chattering.
Hysteresis can be used by combined data width and time width. Hysteresis direction can
be selected from [OFF delay] and[ON delay].
Select in function mode. (F-24, F-25 and F-26 are related functions.)
The default is hysteresis [OFF].
11 Weighing mode
Weight indicator CSD-903
Minebea Intec
EN-111