Ibias =
Bias current used for simulating a starting condition.
Fixed at 100 A per connected DC Current Generator.
Icc =
Specified current increase by the user (dI).
τ
=
Specified time constant by the user (tc).
I =
63% of Icc injected during
τ
, R=U/I.
P0 =
di/dt0
➝
Icc/
τ
➝
U/L.
Measurement results.
The test result is displayed in the following dialog:
To store the result into the current report file, press the ‘Save’ button.
The graph button opens the graph dialog illustrating the performed measurement.
www.megger.com
68
Operation