Code no. 52
Message:
USB Stick already contains a “Report” folder. Overwrite existing files?
Cause:
The operator connected a USB stick that already contains stored reports
Action:
Confirm to begin transferring report files. Reports already on the USB stick using the same
report name as reports from the system will be overwritten.
Cancel to abort the transfer.
Code no. 53
Message:
There are unsaved report entries. Are you sure you wish to exit without saving?
Cause:
The software is being closed while there are unsaved measurements in the ‘Report’ dialog.
Action:
Confirm to discard any unsaved measurements.
Cancel to abort the exit procedure.
Code no. 54
Reserved for secondary injection
Message:
Please connect the voltage output to the µOhm input, then press OK.
This message is shown before the calibration process is started.
Action:
Once the connection is made, press OK to start the calibration process
Code no. 55
Reserved for secondary injection
Message:
No voltage feedback, please ensure the connection is made. Calibration aborted.
This message is shown when no voltage is detected on the µOhm input. The calibration process
cannot continue.
Action:
Please ensure the proper connections are made and then try again.
Code no. 56
Reserved for secondary injection
Message:
Calibration in progress…(%d)
Action:
No action required.
Code no. 57
Reserved for secondary injection
Message:
Output offset calibrated to %d. Measured offset : %.3n V
This message is shown after the calibration process is completed.
Action:
Press OK to return to the return to the menu
Code no. 200
Message:
This program will be terminated. Shutdown Windows?
Cause:
The software is being closed.
Action:
Confirm to shut down the system after closing the software.
Otherwise, the launcher dialog will be shown.
Code no. 201
Message:
Are you sure you want to clear the list of tests?
Cause:
The measurements in the ‘Report’ dialog are being cleared.
Action:
Confirm to clear the measurements table (e.g. for starting a new report).
Cancel to retain the stored measurements.
Code no. 203
Message:
Delete all reports, samples and logfiles from the disk?
Cause:
The operator has pressed ‘Delete’ in the ‘Report’ dialog.
Action:
Confirm to delete all report files stored on this system. This cannot be undone.
Cancel to abort the deletion procedure.
Code no. 204
Message:
Invalid password.
Cause:
The operator has entered an invalid password for a password-protected feature.
Action:
Please enter the correct password.
Code no. 205
Message:
Please fill in the “…” field.