The energy supply consists of:
1. Battery Chargers.
2. Ultracapacitors.
3. Batteries.
1
2
3
Fig 12:
Main Unit: Utilities
Item
Description
1
Compartment for the Battery Charger.
This compartment contains one Benning ADC III rectifier.
The rectifier is based on switch mode technology.
2
Compartment for the Ultracapacitor.
The energy storage module - used as a buffer for the Batteries - is of type 16 V and consists of 6
cells of 3,000 F placed in series.
The compartment contains one module of 16 V.
3
Compartment for the Batteries.
This compartment contains the Batteries, placed in a row of 7 cells connected in series, cells being
2 V 25.0 Ah each.
Type: Enersys Cyclon 0820-0004.
The compartment holds one row
5.2 DC Current Generator Connection Panel.
The connection panel connects the DC Current Generator to the Main Unit.