Example
The following dialog will appear when the button ‘Set I_ref’ is pressed.
Adjusting current increase.
To adjust the duration of the 200 A/s slope, configure the K1 and K2 parameters accordingly in the ‘Auto Mode’
dialog.
K1
Starting Point ‘e’ of the 200 A/s slope
K2
Ending Point ‘f’ of the 200 A/s slope
K1 and K2 are given as a percentage of the specified I_ref.