NOTE :
When upgrading an existing system by adding additional Power Units - for example adding a new
Power Unit to an existing 16,000 A system - a system re-calibration is necessary.
Other examples:
Fault conditions.
The BALTO System may alert the user about technical malfunctions through warning and error messages.
These messages are displayed in the status bar of each dialog, and in the ‘Info’ dialog.
Current Injections may be blocked by some errors. Further testing is only possible once the error is resolved.
Battery Supply.
In each dialog, the levels of the Battery Voltage and Charge Current are displayed.
Green indication:
Battery level optimal for Current Injections.
Orange indication:
Battery is charging, but Current Injections may still be performed.
Red indication:
Battery needs time to recharge, Current Injections are blocked.
Example:
Error display: these messages can be displayed in all dialogs.
www.megger.com
43
Operation