Fiber Cleaning
Cleaning/Inspecting Optical Connectors
B - 1 0
365-372-334 R2.0
Issue 4, November 2004
Figure B-3
Acceptability Criteria for Fiber Cleaning
...........................................................................................................................................................................
Step 3
After the connector has been verified to be cleaned, it should be
immediately inserted into the adapter buildout of the optical
component. This will assure maximum cleanliness and effectiveness of
the connector.
...........................................................................................................................................................................
Step 4
If the cleaned connector can not be immediately connected to a
corresponding adapter, the connector ferrule must be protected with a
connector dust cap. Before placing the cap on the ferrule, make sure the
cap is clean. This can be accomplished by inserting a CLETOP stick
cleaner (swab) of the same inside diameter as the cap (either 2.5 or 1.25
mm) and rotating the stick 360 degrees three (3) times. Following this
procedure, carefully place the cap over the ferrule. When the cleaned
connector is ready for assembly, it should be re-inspected for
cleanliness prior to connection.
End of Steps
...........................................................................................................................................................................
Содержание Metropolis DMXplore
Страница 8: ... C O N T E N T S v i i i 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 16: ... T A B L E S x v i 365 372 334 R2 0 Issue 4 Novmeber 2004 Glossary ...
Страница 224: ... Metropolis DMXplore Access Multiplexer Ring Setup and Testing P A R T x x 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 258: ... Laser Safety and Classifications Metropolis DMXplore Optical Specifications A 8 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 270: ... Fiber Cleaning Cleaning Inspecting Optical Connectors B 1 2 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 286: ... Backplane Pin Replacement Replacement Methods D 1 0 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 292: ... Installation Checklist Overview E 6 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 326: ... G L O S S A R Y G L 3 0 365 372 334 R2 0 Issue 4 November 2004 ...