Equipment and Cable Installation for Metropolis
®
DMXplore Shelf (Rack-Mount)
Power Cable Installation
2 - 1 4
365-372-334 R2.0
Issue 4, November 2004
Figure 2-6
Rack-Mount Metropolis
®
DMX
plore Connector
Important!
To tie RTN-A and RTN-B together use a MESH
Ground Strap to jumper between RTN-COM and GND of the power
terminal block. See Figure 2-7, Power Connection (page 2-15) for
location.
...........................................................................................................................................................................
CAUTION
Verify that the AC/DC converter is not plugged into the AC
power outlet, or that BDCBB breakers are off, or that the BDFB
fuses are not installed.
...........................................................................................................................................................................
Procedure
Step 1
Verify the power source is off.
...........................................................................................................................................................................
Step 2
Connect the A and B power cables to the A and B connector pins of the
terminal block located on the lower left rear of the access panel. Use a
Table 2-3
Power Connections
Shelf Power
Designation
Name
BAT A
-48-A
BAT A
RTN-A
BAT A RTN
BAT B
-48-B
BAT B
RTN-B
BAT B RTN
Содержание Metropolis DMXplore
Страница 8: ... C O N T E N T S v i i i 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 16: ... T A B L E S x v i 365 372 334 R2 0 Issue 4 Novmeber 2004 Glossary ...
Страница 224: ... Metropolis DMXplore Access Multiplexer Ring Setup and Testing P A R T x x 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 258: ... Laser Safety and Classifications Metropolis DMXplore Optical Specifications A 8 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 270: ... Fiber Cleaning Cleaning Inspecting Optical Connectors B 1 2 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 286: ... Backplane Pin Replacement Replacement Methods D 1 0 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 292: ... Installation Checklist Overview E 6 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 326: ... G L O S S A R Y G L 3 0 365 372 334 R2 0 Issue 4 November 2004 ...