...........................................................................................................................................................................................................................................................
Equipment and Cable Installation for Metropolis
®
DMXplore Shelf (Wall-Mount)
Office Alarm Cable Installation
1 - 3 4
365-372-334 R2.0
Issue 4, November 2004
Procedure
Step 1
Obtain the office alarm cable per Table 1-9, Office Alarm Cable
Assemblies (page 1-33). Connect the office alarm cables to the
ALARM terminal block in the lower left hand corner of the access
panel. See Figure 1-14, Office Alarm Cable Connections (page 1-35)
Important!
The recommended wire strip length for cables being
connected to the alarm block is 11mm.
Table 1-10
Office Alarm Connections
Pin#
Color
Name
Designation
1
2
BL
BL/W
CR/MJ
CR/MJ Visual -
RYCRMJV1
3
4
O
O/W
CR/MJ A
CR/MJ Audible -
RYCRMJA1
5
6
G
G/W
MN/ABN
MN/ABN Visual -
RYMNABNV1
7
8
BR
BR/W
MN/ABN A
MN/ABN Audible -
RYMNABNA1
Notes:
1. The SYSCTL circuit pack reports office alarms.
Содержание Metropolis DMXplore
Страница 8: ... C O N T E N T S v i i i 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 16: ... T A B L E S x v i 365 372 334 R2 0 Issue 4 Novmeber 2004 Glossary ...
Страница 224: ... Metropolis DMXplore Access Multiplexer Ring Setup and Testing P A R T x x 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 258: ... Laser Safety and Classifications Metropolis DMXplore Optical Specifications A 8 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 270: ... Fiber Cleaning Cleaning Inspecting Optical Connectors B 1 2 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 286: ... Backplane Pin Replacement Replacement Methods D 1 0 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 292: ... Installation Checklist Overview E 6 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 326: ... G L O S S A R Y G L 3 0 365 372 334 R2 0 Issue 4 November 2004 ...