Equipment and Cable Installation for Metropolis
®
DMXplore Shelf (Wall-Mount)
Power Cable Installation
...........................................................................................................................................................................................................................................................
1 - 2 1
365-372-334 R2.0
Issue 4, November 2004
...........................................................................................................................................................................
Step 5
If not using the orderable AC/DC converter (C), verify that the
converter is fuse limited to
2-amperes
on each lead.
Important!
If the AC/DC converter is not fuse limited to 2
-
amperes
, it will be necessary to add a 2A inline fuse for each power
lead.
...........................................................................................................................................................................
Step 6
Proceed to
Step 9.
...........................................................................................................................................................................
Step 7
Splice feeders from the BDCBB or BDFB to the Metropolis
®
DMXplore power cables. Refer to Table 1-3, Power Connections (page
1-18).
Important!
Four wires are spliced to the power cables:
1.
BAT A
2.
BAT A RTN
3.
BAT B
4.
BAT B RTN
...........................................................................................................................................................................
Step 8
Label the feeders at the power source as follows:
1.
BAT A
2.
BAT A RTN
3.
BAT B
4.
BAT B RTN
Important!
Each feeder should be fused for 2-amperes.
...........................................................................................................................................................................
Step 9
Leave the power supply mechanism disconnected at the power source
until you are ready to perform the procedures in Chapter 3, Powering
and Initial Circuit Pack Installation for Metropolis
®
DMXplore Shelf
(Wall-Mount) of this manual.
Содержание Metropolis DMXplore
Страница 8: ... C O N T E N T S v i i i 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 16: ... T A B L E S x v i 365 372 334 R2 0 Issue 4 Novmeber 2004 Glossary ...
Страница 224: ... Metropolis DMXplore Access Multiplexer Ring Setup and Testing P A R T x x 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 258: ... Laser Safety and Classifications Metropolis DMXplore Optical Specifications A 8 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 270: ... Fiber Cleaning Cleaning Inspecting Optical Connectors B 1 2 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 286: ... Backplane Pin Replacement Replacement Methods D 1 0 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 292: ... Installation Checklist Overview E 6 365 372 334 R2 0 Issue 4 November 2004 ...
Страница 326: ... G L O S S A R Y G L 3 0 365 372 334 R2 0 Issue 4 November 2004 ...