L-DALI User Manual
338
LOYTEC
Version 5.2
LOYTEC electronics GmbH
Property Identifier
Property
ID
Property Datatype
Conformance
Code
Object_Identifier
75
BACnetObjectIdentifier
R
Object_Name
77
CharacterString
R
Object_Type
79
BACnetObjectType
R
Present_Value
85
BACnetBinaryPV
R
Status_Flags
111
BACnetStatusFlags
R
Event_State
36
BACnetEventState
R
Reliability
103
BACnetReliability
R
Out_Of_Service
81
BOOLEAN
W
Polarity
84
BACnetPolarity
W
Inactive_Text
46
CharacterString
W
Active_Text
4
CharacterString
W
Profile_Name
168
CharacterString
R
Debounce
535
Unsigned
W
Unoccupied_Delay
536
Unsigned
W
Heartbeat
558
Unsigned
W
Table 37: Properties of the Binary Input object representing a DALI occupancy sensor.
Object_Identifier (Read-Only)
The instance number is equal to the instance number of the corresponding Analog Input
object (see Section 8.3.4.2).
Object_Name (Read-Only)
This property holds the value of the
Object_Name
of the associated Analog Input object
with the addition “
Occupancy
”.
Object_Type (Read-Only)
The value of this property is BINARY_INPUT (3).
Present_Value (Read-Only)
This property reports the occupancy status. If the
Polarity
property is
NORMAL
the
occupied state corresponds to
ACTIVE
, while the unoccupied state corresponds to
INACTIVE
.
Status_Flags (Read-Only)
Of the four flags the flags IN_ALARM, FAULT, and OUT_OF_SERVICE are linked to the
state of the corresponding properties
Event_State
,
Reliability
and
Out_Of_Service
as
described by the standard.
OVERRIDDEN
Always FALSE.
Reliability (Read-Only)
The
Reliability
property for this object type may have any of the following values:
NO_FAULT_DETECTED
No fault was detected.