3.
Check the additional properties. Checking the
Read
box will add an input data point,
checking the
R/W
box will add a value data point.
4.
Click
Close
. The selected data point can now be expanded with the plus icon and show
its additional properties as sub-data points.
5.
To remove properties perform the same steps and uncheck the corresponding check-
boxes. Alternatively, select the property (or more) and press the
Delete
key.
7.8.9 Enable International Character Support
By default BACnet objects on the device contain ASCII strings in properties such as object
name, description, active/inactive text, state texts. This is the setting most third-party tools
are interoperable with. To support international character sets, the device can be configured
to expose strings as ISO-8895-1 (for most Western European languages) or UCS-2 (for
Unicode character sets such as Japanese).
To Enable International Character Support
1.
In the Configurator software menu go to
Settings
Project settings …
. This opens
the
Project Settings
dialog (see also Section 7.16.5).
2.
Click on the tab
BACnet
.
3.
Put a check mark either on
ASCII/UTF-8
(default),
UCS-2
(Unicode, e.g., for
Japanese), or
ISO-8859-1
(for Western European languages).
4.
Click
OK.
5.
Download the configuration to activate the change.
7.8.10 Read the Active Priority
In BACnet objects that possess a priority array the effective value depends on the used write
priority slots. A special data point on the device can be added that allows reading out the
active priority of such an object, giving a value between 1 and 16.
To Read the Active Priority of a Local Object
1.
Select the BACnet server object for adding properties.
2.
Right-click on the data point and select
Add/Remove BACnet properties …
from the
context menu. The dialog for mapping BACnet properties to data points appears.
3.
For the Present_Value select the additional box Active Priority.
To Read the Active Priority of a Feedback Value
1.
Select a write client mapping.
2.
Right-click on the data point and select
Create Priority Feedback Point
from the
context menu.