L-DALI User Manual
114
LOYTEC
Version 5.2
LOYTEC electronics GmbH
System Temp
: This register is an
analog
data point. It displays the currently measured
system temperature in degrees Celsius. Example: 39 °C.
Application Vendor, Authentication Code,
and
Authentication Result
: These
registers can be used to implement an IP protection mechanism for application
programs, such as IEC61131 programs.
Serial Number
: This register is a
string
data point. It displays the device’s serial
number as an ASCII string. Example: “011401-000AB001D1E4”.
MAC Address
: This register is a
user
data point. It displays the device’s MAC address
as an array of 6 hexadecimal Bytes. Example: 000AB001D1E4.
Firmware Version
: This register is a
string
data point. It displays the device’s
firmware version as an ASCII string. Example: “4.1.0”.
Device IP Address
: This register is a
string
data point. It displays the device’s IP
address as an ASCII string. Example: “10.101.18.204”.
Device IP Port
: This register is an
analog
data point. It displays device’s HTTP port
as an integer value. Example: 80.
TZ Offset
: This register is an
analog
data point. It displays the time zone offset relative
to UTC in seconds. This means a positive value for a time zone, which lies east of
Greenwich. The offset includes daylight savings time. The local time can be derived by
adding this register to the system time register. Example: +7200 for GMT+1 (Paris,
Berlin, Vienna) including DST.
Device Status
: This register is a
string
data point. It contains an XML document with
the device status file contents. It is not displayed on the Web UI.
Ethernet Link Mask
: This register is a
multistate
data point. It displays the link
information of the Ethernet port. Example: “Eth 1”.
Hostname
: This register is a
string
data point. It displays the host name, which has
been configured in the IP settings. Example: “my_linx”.
Position Longitude
: This register is an
analog
data point. It displays the longitude part
of the device’s location in degrees. Writing to the corresponding data point
Position
Longitude_Set
sets the device’s longitude in degrees. Example: -16.33472.
Position Latitude
: This register is an
analog
data point. It displays the latitude part of
the device’s location in degrees. Writing to the corresponding data point
Position
Latitude_Set
sets the device’s latitude in degrees. Example: 48.22056.
Position Altitude
: This register is an
analog
data point. It displays the altitude of the
device’s location in meters above sea level. Writing to the corresponding data point
Position Altitude_Set
sets the device’s altitude in meters above sea level. Example:
200 m.
Secure Mode
: On models providing a firewall, this binary register enable the firewall
to restrict access to the services provided in the
Secure Services
register.
Secure Services
: On models providing a firewall, this string register selects the
services which should be available when
Secure Mode
is
TRUE
. This registers accepts
a space-separated list of service names. If the selected services would make the device
unconfigurable, a default configuration with HTTPS and SSH enabled is selected. The
available service names are:
o
HTTP
: Enables access to the configuration pages via HTTP.
o
HTTPS
: Enables access to the configuration pages via HTTPS.
o
SSH
: Enables access to the SSH server.
o
OPC
: Enables access to the OPC XML-DA server.
o
OPCUA
: Enables access to the OPC UA server.