L-DALI User Manual
301
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nviFrost
Type
SNVT_switch
Valid Range
.value:
0..100%
.state:
0, 1
Frost:
.state=1 and .value>=0.5%
No Frost: .state=0 and .value=0
Default Value
Description
This network variable input provides the frost status.
If a frost condition is detected, the sunblinds must not move.
nviDawn
Type
SNVT_switch
Valid Range
.value:
0..100%
.state:
0, 1
Dawn:
.state=1 and .value>=0.5%
No Dawn: .state=0 and .value=0
Default Value
Description
Currently not used.
nviDusk
Type
SNVT_switch
Valid Range
.value:
0..100%
.state:
0, 1
Dusk:
.state=1 and .value>=0.5%
No Dusk: .state=0 and .value=0
Default Value
Description
Currently not used.
nviOutdoorTemp
Type
SNVT_temp_p
Valid Range
-273.17°C..327.66°C
Resolution: 0.01°C
Default Value
Description
This network variable input provides the current outdoor temperature. This input is used when the
sunblinds are used to heat/cool a room (see Section 8.2.9.3).