L-DALI User Manual
304
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nciWeaSenFailPos
Type
SCPTdefaultSetting (SNVT_setting)
Valid Range
.function:
SET_NUL (-1):
Invalid Value
SET_DOWN (2) Decrease setting by specified value
SET_UP (3)
Increase setting by specified value
SET_STOP (4)
Stop action
SET_STATE (5) Setting on at specified value
.setting:
0..100, resolution 0.5
.rotation: -359.98 .. 360.00, resolution 0.02
Default Value
SET_STATE, 0%, 0 deg
Description
This configuration property defines the safety position of sunblinds when a failure of a safety
relevant weather sensor (e.g.
nviWindspeed
,
nviRain
or
nviFrost
) is detected.
nciInvWinCon
Type
UCPTautoOffBreak (SNVT_lev_disc)
Valid Range
ST_ON, ST_OFF
Inverted: ST_ON
Not Inverted: ST_OFF
Default Value
ST_OFF (not inverted)
Description
This configuration property allows inverting the window contact inputs of the sunblind controllers
(
nviWindowContact
).
nciTermTempHyst
Type
SCPTtemperatureHysteresis (SNVT_temp_diff_p)
Valid Range
-327.68°C..327.66°C
Resolution: 0.01°C
Default Value
1°C
Description
This configuration property defines the hysteresis for the outdoor temperature (
nviOutdoorTemp
).
It is used for the heating/cooling algorithm (see Section 8.2.9.3).
nciTermSLHyst
Type
UCPTterminalLoadSLhysteresis (SNVT_lev_cont)
Valid Range
0..100%
Resolution: 0.5
Default Value
5.0%
Description
This configuration property defines the hysteresis for the sun lux level input (
nviSunLux
). It is
used by the heating/cooling algorithm (see Section 8.2.9.3).