L-DALI User Manual
218
LOYTEC
Version 5.2
LOYTEC electronics GmbH
4.
Enter a
Log Size
, which defines how many transitions are resident in the alarm log.
5.
Select the desired
Fill Mode
. The default is
Ring Buffer
, which lets the log overwrite
old records once it reaches its capacity. Select
Linear Buffer
, if recording shall be
stopped in this case. The user has to purge the log before it continues recording.
6.
Define a percentage for
Fill Level Notification
, which can be used to trigger the
transmission of E-Mails.
7.
Click on the button
Add…
on top of the
Logged Alarm Objects
list.
8.
A data point selector dialog opens. Select one or more alarm objects that shall be
logged and click
OK
. The alarm objects appear in the list.
9.
Click
Create
to create the alarm log object.
7.12.5 Multi-Edit Alarm Conditions
For editing a large number of alarm conditions, some multi-edit features are available to
assist in this task. On a multi-selection of data points, the user can execute two options from
the context menu:
Configure Alarm Conditions
: Use this option from the context menu on a multi-
selection of data points. The alarm condition of all selected data points can be edited. If
all selected data points are of the same class (e.g., all analog data points) the alarm
condition can be fully specified. Note that these settings will be applied to all data
points. In alarm messages use variable place holders. For assigning different limit and
enable data points use the manage relations tab (see Section 7.7.8).
Configure Alarm Messages
: Use this option from the context menu for editing alarm
messages (alarm, clear, fault) for all data points in the selection. A dialog with a
spreadsheet view appears as shown in Figure 198. Edit the messages directly in the
spreadsheet. Alternatively, click on the export button
to export the spreadsheet as a
CSV file for editing in Excel. Import a CSV file with alarm messages in the menu
Tools
Import alarm messages
.
Note:
Use the feature to include data points from sub-folders and filter expressions to expand the
ability to perform a multi-select.
Figure 198: Spreadsheet for multi-edit of alarm messages.