L-DALI User Manual
264
LOYTEC
Version 5.2
LOYTEC electronics GmbH
Default Connection
Condition
Lux Level
The default connection applies if the following network variables
are not bound:
nviLuxLevel
(Constant Light Controller X)
nviOccup
(Constant Light Controller X)
Occupancy State
The default connection applies if the following network variables
are not bound:
nviLuxLevel
(Constant Light Controller X)
nviOccup
(Constant Light Controller X)
Lamp Value
The default connection applies if the following network variables
are not bound:
nvoLampValue
(Constant Light Controller X)
nviGPValue
(Group Object X)
nviGPSetting
(Group Object X)
nviGPOverride
(Group Object X)
nviGPScene
(Group Object X)
Table 22: Default Connections for Automatic Internal Bindings.
When using local DALI sensors and/or DALI groups internal manual CLC bindings can be
configured (see Section 5.3.2 and 7.6). The Web-Interface for CLC Bindings can also be
used to verify the current status of all bindings (internal and NVs).
8.2.8.2 Setpoint
The desired setpoint for the illumination level is configured via the configuration property
nciLuxSetpoint
. The input network variable
nviCLSetting
of type SNVT_setting switches
the constant light controller on or off. Furthermore this network variable can be used to
temporarily adjust the setpoint.
8.2.8.3 Operating Modes
The operating mode of the constant light controller is set via the configuration property
nciCLMode
. Table 23 shows the different operating modes and under which conditions they
are used: