L-DALI User Manual
294
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nciBypassTime
Type
SCPTbypassTime (SNVT_time_min)
Valid Range
0..65,535 minutes
Default Value
0
Description
This configuration property defines the amount of time that the sunblind controller is in bypass
(occupancy) mode following a single bypass request via
nviOccManCmd
. Additional bypass
requests can restart the timer. Setting this configuration property to zero disables the bypass
function and no bypass takes place.
nciOverrideValue
Type
SCPTdefaultSetting (SNVT_setting)
Valid Range
.function:
SET_NUL (-1):
Invalid Value
SET_DOWN (2) Decrease setting by specified value
SET_UP (3)
Increase setting by specified value
SET_STOP (4)
Stop action
SET_STATE (5) Setting on at specified value
.setting:
0..100, resolution 0.5
.rotation: -359.98 .. 360.00, resolution 0.02
Default Value
SET_NUL
Description
This configuration property defines the override value which is adopts by the sunblind when the
nviOverride
is at ON.
nciMaintValue
Type
SCPTdefaultSetting (SNVT_setting)
Valid Range
.function:
SET_NUL (-1):
Invalid Value
SET_DOWN (2) Decrease setting by specified value
SET_UP (3)
Increase setting by specified value
SET_STOP (4)
Stop action
SET_STATE (5) Setting on at specified value
.setting:
0..100, resolution 0.5
.rotation: -359.98 .. 360.00, resolution 0.02
Default Value
SET_NUL
Description
This configuration property defines the maintenance value which is adopts by the sunblind when
the
nviMaintenance
is at ON.
nciDriveDelay
Type
UCPTdriveDelay (SNVT_time_sec)
Valid Range
0..6553.4 sec
Resolution: 0.1 sec
Default Value
0.0 sec (no delay)
Description
This configuration property defines the delay which the sunblind controller waits before it updates
its outputs. If different drive delays are configured for the different sunblind controllers, the
sunblinds will not drive at the same time avoiding a power peak. No drive delay is applied for
local control (
nviLocalControl
).