![LOYTEC L-DALI Скачать руководство пользователя страница 274](http://html1.mh-extra.com/html/loytec/l-dali/l-dali_user-manual_1943336274.webp)
L-DALI User Manual
274
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nciCLMode
Type
UCPTclMode (byte)
Valid Range
CL_MODE_DISABLED
CL_MODE_REGULATOR
CL_MODE_CONTROL
CL_MODE_UPDATER
CL_MODE_PRESENCE
CL_MODE_REGULATOR_NO_OCC
CL_MODE_CONTROL_NO_OCC
CL_MANUAL_ON_AUTO_OFF
CL_MODE_REGULATOR_AUTO
CL_MODE_CONTROL_AUTO
CL_MODE_PRESENCE_AUTO
CL_MODE_AMBIENT
CL_MODE_REGULATOR_BEDROOM
CL_MODE_PRESENCE_BEDROOM
Default Value
CL_MODE_DISABLED
Description
This configuration property defines the operating mode of the constant light controller.
Operating Mode
Description
REGULATOR
A light sensor that measures the indoor illumination is
installed.
An occupancy sensor is installed.
REGULATOR_NO_OCC
A light sensor that measures the indoor illumination is
installed.
No occupancy sensor is installed.
REGULATOR_AUTO
Similar to REGULATOR, but a manual override is
automatically relinquished when the room becomes
unoccupied.
REGULATOR_BEDROOM
Similar to REGULATOR_AUTO, but a manual override is
not automatically relinquished when the lights are
overridden to off.
CONTROL
A light sensor that measures the outdoor illumination is
installed.
An occupancy sensor is installed.
CONTROL_NO_OCC
A light sensor that measures the outdoor illumination is
installed.
No occupancy sensor is installed.
CONTROL_AUTO
Similar to CONTROL, but a manual override is
automatically relinquished when the room becomes
unoccupied.
CONTROL_BEDROOM
Similar to CONTROL_AUTO, but a manual override is not
automatically relinquished when the lights are overridden to
off.
PRESENCE
Based on occupancy the lights shall be switched on and off.
PRESENCE_AUTO
Similar to PRESENCE, but a manual override is
automatically relinquished when the room becomes
unoccupied.
MANUAL_ON_AUTO_OFF
Lights are switched on manually, but shall be switched off
when the room becomes unoccupied.
AMBIENT
Effect or ambient lighting is switched on based on the
measured illumination level (switching on ambient lights
does not influence measured illumination level).
UPDATER
A DALI sensor with constant light controller functionality
shall be mapped to the CEA-709 network. Only the setpoint