L-DALI User Manual
287
LOYTEC
Version 5.2
LOYTEC electronics GmbH
nviSBSettingFB
Type
SNVT_setting
Valid Range
.function:
SET_NUL (-1):
Invalid value.
SET_DOWN (2) Decrease setting by specified value.
SET_UP (3)
Increase setting by specified value.
SET_STOP (4)
Stop action.
SET_STATE (5) Setting on at specified value.
.setting:
0..100, resolution 0.5
.rotation: -359.98 .. 360.00, resolution 0.02
Default Value
-
Description
Feedback from sunblind actuator of type
SNVT_setting
.
nviSBStateFB
Type
SNVT_sblnd_state
Valid Range
.pos.function:
SET_NUL (-1):
Invalid value.
SET_DOWN (2) Decrease setting by specified value.
SET_UP (3)
Increase setting by specified value.
SET_STOP (4)
Stop action.
SET_STATE (5) Setting on at specified value.
.pos.setting:
0..100, resolution 0.5
.pos.rotation:
-359.98 .. 360.00, resolution 0.02
.cmd_source:
SBCS_NUL, SBCS_LOCAL, SBCS_GROUP, …
.error_code:
SBE_NUL, SBE_NO_ERROR, SBE_IN_PROGRESS, …
Default Value
-
Description
Feedback from sunblind actuator of type
SNVT_sblnd_state
.
nviIndoorTemp
Type
SNVT_temp_p
Valid Range
-273.17°C...327.66°C
Resolution: 0.01°C
Default Value
-
Description
This network variable input provides the room temperature measured by a temperature sensor.
This input is used if the sunblinds are used for heating/cooling (see Section 8.2.9.3).
nviTerminalLoad
Type
SNVT_lev_percent
Valid Range
-163.840..163.830
Resolution: 0.005
Default Value
Description
This network variable input is used if the sunblinds are used for heating/cooling (see Section
8.2.9.3). The input informs the controller of the current heating/cooling demand. Positive values
indicate that cooling energy is required, while negative values indicate that heating energy is
required.
If the network variable in not bound, the heating/cooling feature is disabled.