Figure 217: Timing of occupancy detection.
8.2.7.2 Output Network Variables
nvoOccup
Type
SNVT_occupancy
Valid Range
OC_NUL (-1):
Invalid Value
OC_OCCUPIED (0):
Area is occupied
OC_UNOCCUPIED (1): Area is unoccupied
OC_BYPASS (2):
Area is temporarily occupied for the bypass period
OC_STANDBY (3):
Area is temporarily unoccupied
Default Value
OC_NUL
Description
This network variable provides the occupancy state measured by the occupancy sensor.
If no corresponding occupancy sensor is present on the DALI network the value is OC_NUL.
8.2.7.3 Configuration Properties
All configuration properties listed in this section are implemented as Configuration
Parameters using configuration files (CPT, CPV, and CPC files). File access is provided via
L
ON
M
ARK
FTP.
nciHeartBeat
Type
SCPTheartbeat (SNVT_time_sec)
Valid Range
0..6553.4 sec
Resolution: 0.1 sec
Default Value
120.0 sec
Description
Maximum period of time that expires before the object automatically transmits the present value
of the