channels (see Section 8.3.3.10). During this time the lamps will only be switched to on
(100%) or off (0%) but not dimmed.
8.3.3.9 Fail Safe Functions
The light level a lamp adopts after power-up is defined in the property
Power_On_Level
.
The light level a lamp adopts in case of a DALI system failure is defined in the
configuration property
System_Failure_Level
. Both are available via Analog Output objects
corresponding to DALI ballasts (see Section 8.3.3.10).
8.3.3.10
Analog Output Object
– Control DALI ballast, group, or channel
This object type is used to control the dim level of DALI ballasts (see Table 28), DALI
groups (see Table 29), or DALI channel (see Table 30). For DALI devices it also provides
access to all its DALI parameters. Further, parameters for light controller applications are
available (e.g. staircase lighting, on and off delays, off warning etc.).