Only present if the object is associated with a DALI channel.
Lamp_Failure (Read-Only)
The value of this proprietary property (property ID 531) is a 64-bit wide BIT STRING. It
contains one bit for each ballast on the channel. If the device reports a lamp failure the bit is
set, otherwise it is cleared.
Only present if the object is associated with a DALI channel.
Battery_Failure (Read-Only)
The value of this proprietary property (property ID 532) is a 64-bit wide BIT STRING. It
contains one bit for each ballast on the channel. If the device reports a battery failure (self-
contained emergency lights only) the bit is set, otherwise it is cleared.
Only present if the object is associated with a DALI channel.
Function_Test_Failure (Read-Only)
The value of this proprietary property (property ID 533) is a 64-bit wide BIT STRING. It
contains one bit for each ballast on the channel. If the device reports a function test failure
(self-contained emergency lights only) the bit is set, otherwise it is cleared.
Only present if the object is associated with a DALI channel.
Duration_Test_Failure (Read-Only)
The value of this proprietary property (property ID 534) is a 64-bit wide BIT STRING. It
contains one bit for each ballast on the channel. If the device reports a duration test failure
(self-contained emergency lights only) the bit is set, otherwise it is cleared.
Only present if the object is associated with a DALI channel.
Intrinsic reporting
The object supports all properties required for intrinsic reporting. Per default no alarms are
enabled.
8.3.4 Sensor Objects
The L-DALI provides objects for 16 DALI sensors per channel. Each sensor is represented
by
an Analog Input object providing the lux level measured by the sensor and
an Binary Input object providing the occupancy state determined by the sensor.
8.3.4.1 Sensor Calibration
To provide a reliable measurement the light sensor needs to be calibrated. The calibration is
best performed using the Web Interface (refer to Section 5.3.4.6).
8.3.4.2 Analog Input Object
– DALI lux level sensor
This object is used to represent the light sensor part of a DALI Sensor (see Table 36). There
is a maximum of 16 such objects per channel.