![LOYTEC L-DALI Скачать руководство пользователя страница 336](http://html1.mh-extra.com/html/loytec/l-dali/l-dali_user-manual_1943336336.webp)
L-DALI User Manual
336
LOYTEC
Version 5.2
LOYTEC electronics GmbH
Property Identifier
Property
ID
Property Datatype
Conformance
Code
Object_Identifier
75
BACnetObjectIdentifier
R
Object_Name
77
CharacterString
R
Object_Type
79
BACnetObjectType
R
Present_Value
85
REAL
R
Device_Type
31
CharacterString
R
Status_Flags
111
BACnetStatusFlags
R
Event_State
36
BACnetEventState
R
Reliability
103
BACnetReliability
R
Out_Of_Service
81
BOOLEAN
W
Units
117
BACnetEngineeringUnits
R
Min_Pres_Value
69
REAL
R
Max_Pres_Value
65
REAL
R
COV_Increment
22
REAL
W
Time_Delay
113
Unsigned
W
Notification_Class
17
Unsigned
W
High_Limit
45
REAL
W
Low_Limit
59
REAL
W
Deadband
25
REAL
W
Limit_Enable
52
BACnetLimitEnable
W
Event_Enable
35
BACnetEventTransitionBits
W
Acked_Transitions
0
BACnetEventTransitionBits
W
Notify_Type
72
BACnetNotifyType
W
Event_Time_Stamps
130
BACnetARRAY[3] of BACnetTimeStamp
R
Profile_Name
168
CharacterString
R
Lux_2
557
REAL
R
Table 36: Properties of the Analog Input object representing a DALI lux level sensor.
Object_Identifier (Read-Only)
The default instance number is 5BCC, where “B” is the DALI interface number (0-3) in
decimal, and “CC” is the DALI device number (00-15). Example: DALI sensor 4 on
channel 2 has the instance number 5104.
Object_Name (Read/Write)
This property holds the name of the DALI sensor. It can be changed via the Web-UI.
Object_Type (Read-Only)
The value of this property is ANALOG_INPUT (0).
Present_Value (Read-Only)
This property reports the current light level reported by the sensor corrected by the
calibration function configured via the gain table (see Section 8.3.4.1).