IF55 ROT CANopen®
Scaling function control
If this option is disabled (bit 2 = 0), the device uses the physical singleturn
resolution and the physical multiturn resolution to arrange the absolute
position information (see the
2200-04 Physical Singleturn Resolution [bits]
2200-05 Physical Multiturn Resolution [bits]
6502-00 Number of distinguishable revolutions
objects are automatically set accordingly). The values set in the
Programmable pulse per revolution
objects are ignored.
On the contrary, if it is enabled (bit 2 = 1), the system will use the values set in
the
6001-00 Programmable pulse per revolution
Programmable total measuring range
objects to calculate the position
information.
The relation between the
6001-00 Programmable pulse per revolution
6002-00 Programmable total measuring range
objects is as follows:
Transmitted position =
6001-00 Programmable pulse per
real position
WARNING
When you enable the scaling function (bit 2
please enter scaled values next to the
6001-00 Programmable pulse per
6002-00 Programmable total measuring range
are consistent with the physical values.
WARNING
Every time you enable the scaling function and/or change the scaling values (see
the
6001-00 Programmable pulse per revolution
Programmable total measuring range
objects), then you are required to set a
object).
NOTE
object (see on page 60) is set to “1”
= enabled, the scaling function -if set differently from default- is ignored.
MAN IF55 ROT CB E 1.2.odt
6 - CANopen® interface (DS 406)
62 of 88