IF55 ROT CANopen®
6200-00 Cyclic timer
[Unsigned16, rw]
The cyclic timer value is used in asynchronous transmission mode
(
Transmission Type
= FEh) to set the interval between two PDO issues.
≠
0, the PDO message is
sent cyclically and the interval between two messages is the time set next to the
object; otherwise, if the value next to the
object = 0, the PDO message is not sent.
The value is expressed in milliseconds. See on pages 44 and 50 ff.
Default = 0000h
Master
Encoder
COB-ID
Cmd
Index
Sub
Process data
600+ID
2B
00
62
00
64
00
-
-
Encoder
Master
COB-ID
Cmd
Index
Sub
Process data
580+ID
60
00
62
00
00
00
-
-
NOTE
Refer to the “7 - Setting-up” section on page 81 for an example of setting the
object.
6500-00 Operating status
[Unsigned16, ro]
Bit
Function
bit = 0
bit = 1
0
CW
(clockwise)
CCW
(counter-clockwise)
1
not used
2
Disabled
Enabled
3 … 11
not used
12
position >
position <
13
position <
position >
14
not used
15
Stopped
/
Pre-operational
Operational
MAN IF55 ROT CB E 1.2.odt
6 - CANopen® interface (DS 406)
70 of 88