IF55 ROT CANopen®
3.2 Installation on panel (Figure 2)
Figure 2
The unit is designed for installation on the even surface of a panel.
The back flange
2
is fitted with four holes for inserting the fixing screws
1
.
Tighten the four fixing screws
1
until the unit is properly fastened to the
support. Use
four M3 8 mm min. long cylinder head screws
. The
recommended tightening torque is
1.1 Nm
.
3.3 Installation with DIN rail clip (Figure 3)
The unit can be installed on DIN profiles inside a rack. A clip
3
for direct fitting
on DIN TS35 rails is supplied for free. It has to be fixed on the back of the flange
2
by means of the provided screw
4
.
WARNING
To mount the clip
3
you need to remove the cap
5
and drill a hole
A
in the back
flange
2
. Delicate electronic circuits and wirings are located inside the cap
5
.
Thus this operation has to be accomplished by skilled personnel only. Please pay
careful attention and observe great precaution when carrying out this
operation.