89
Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Alarm ID
Alarm Screen Line 1
Alarm Screen Line 2
Reset Type
Lockout
Action Type
Notes
80
Supply Water Temp 1
Sensor Value Not Valid
Auto
Disable Compressors
WSHP
81
Return Water Temp 1
Sensor Value Not Valid
Auto
Disable Compressors
WSHP
82
Reac Whl In Temp
Sensor Value Not Valid
Auto
50% DFF Control
83
Reac Whl Out Temp
Sensor Value Not Valid
Auto
Informational
84 - 85
Cold Coil (x) Temp
Sensor Value Not Valid
Auto
Disable Cooling Ramp
86 - 87
Cold Coil (x) RH
Sensor Value Not Valid
Auto
Informational
88
Return Filter Pressure
Sensor Value Not Valid
Auto
Informational
89
Space 1 CO2
Sensor Value Not Valid
Auto
Disable CO
2
90
Space Static Pressure
Sensor Value Not Valid
Auto
Informational
91
OA Filter Pressure
Sensor Value Not Valid
Auto
Informational
92
Supply Duct Stat Press Sensor Value Not Valid
Auto
Disable Static Press Control
93
Return Duct Stat Press Sensor Value Not Valid
Auto
Disable Static Press Control
94 - 97
Sup Fan (x) AFMS
Sensor Value Not Valid
Auto
Informational
98 - 101
Ret Fan (x) AFMS
Sensor Value Not Valid
Auto
Informational
102 -105
Exh Fan (x) AFMS
Sensor Value Not Valid
Auto
Informational
106
Min Outside Dmpr AFMS
Sensor Value Not Valid
Auto
Informational
107
Outside Damper AFMS
Sensor Value Not Valid
Auto
Informational
108
HW Exhaust Pressure
Sensor Value Not Valid
Auto
Disable Wheel Ex Bypass
Heat Wheel
109
HW Supply Pressure
Sensor Value Not Valid
Auto
Disable Wheel Ex Bypass
Heat Wheel
110 - 121
Zone (x) Space Temp
Sensor Value Not Valid
Auto
Disable Zone Control
122
Space Setpt Adj Slider
Sensor Value Not Valid
Auto
Informational
123
Space 2 CO2
Sensor Value Not Valid
Auto
Disable CO2
124
Return CO2
Sensor Value Not Valid
Auto
Disable CO2
125 - 132
Discharge Press Ckt (x) Sensor Value Not Valid
Auto
Disable Compressor Circuit
133 - 140
Suction Press Ckt (x)
Sensor Value Not Valid
Auto
Disable Compressor Circuit
Only with
EVD
141 - 148
Discharge Temp Ckt (x) Sensor Value Not Valid
Auto
Disable Compressor Circuit
Only with
EVD
149 - 156
Suction Temp Ckt (x)
Sensor Value Not Valid
Auto
Disable Compressor Circuit
Only with
EVD
157 - 164
High Disch Temp Ckt (x) Compressors Disabled
Auto
Disable Compressor Circuit
165 - 172
High Superheat Ckt (x)
Compressors Disabled
Manual
Disable Compressor Circuit
173 - 180
Low Superheat Ckt (x)
Auto
Disable Compressor Circuit
181 - 188
High Compression
Ckt (x) Comps Disabled Auto until Lockout 3x in 1 hr Disable Compressor Circuit
189 - 196
High Suction Pressure Ckt (x) Comps Disabled Auto until Lockout 3x in 1 hr Disable Compressor Circuit
197 - 204
Low Condenser Pressure Ckt (x) Comps Disabled Auto until Lockout 3x in 1 hr Disable Compressor Circuit
205 - 212
Ckt A High Saturated
Discharge Temperature
Auto
Disable Compressor Circuit
213 - 220
Ckt A Low Saturated
Suction Temperature
Auto
Disable Compressor Circuit
221
Supply Air Temperature
Low Limit Shutdown
Manual
Shutdown Unit
222
Heat Wheel Rotation
Not Detected
Auto
Informational
223 - 226
Slave Unit (x) Offline
Auto
Informational
227
Master Unit Offline
Auto
Disable Slave Mode
228 - 235
Ckt (x) Abnormal Press Compressors Disabled
Auto
Disable Compressor Circuit
236
Heat Pump Defrost
Mode is Active
Auto
3x in 1 hr
Informational
237
Multi Devices per Ch
Contact Unison
Auto
Informational
238 -239
Exp Board (x) Failure
Board is Offline
Auto
Shutdown Unit
240
Shutdown Contact
In Alarm Position
Auto
Shutdown Unit
241
Cold Deck Temperature Sensor Value Not Valid
Auto
Disable Cold Deck Control
242
Hot Deck Temperature
Sensor Value Not Valid
Auto
Disable Hot Deck Control
Table 48: Alarm Data, continued.
Alarm ID
Alarm Screen Line 1
Alarm Screen Line 2
Reset Type
Lockout
Action Type
Notes
243
Neutral Deck Temp
Sensor Value Not Valid
Auto
Informational
244
Comp Maint Alarm
Run Hours Spt Reached
Manual
Informational
245
Supply Air Temperature
High Limit Shutdown
Manual
Shutdown Unit
246
Space High Static Pres
Shutdown
Manual
Shutdown Unit
247 - 254
Liquid Pres Ckt (x)
Sensor Value Not Valid
Auto
Switch to Discharge or
100% Cond Fan
255
Internal Board Temp
Exceeds -40F or 158F
Auto
Informational
256
Regeneration Fan Run
Status Not Proven
Auto
Disable Regen Control
257 - 264
Water Flow Ckt (x)
Flow Switch not made
Manual
Disable Compressor
Circuit
265
Pre Cooling Coil Temp
Sensor Value Not Valid
Auto
Disable PreCooling
266
Post Cooling Coil Temp
Sensor Value Not Valid
Auto
Informational
267
BMS Offline
Watchdog is FALSE
Auto
Local Control
268 - 275
Liquid Temp Ckt (x)
Sensor Value Not Valid
Auto
Switch to Discharge or
100% Cond Fan
276
Clg Coil Setpt Input
Value is not valid
Auto
Informational
Controls Lite - Setpt
Mode
277
Sup Air Setpt Input
Value is not valid
Auto
Informational
Controls Lite - Setpt
Mode
278
Cond Circuit (x)
Overload Tripped
Auto
Disable Compressor
Circuit
286
Supply Fan
Overload Tripped
Auto
Informational
287
Exhaust Fan
Overload Tripped
Auto
Informational
288
Generic Fan
Overload Tripped
Auto
Informational
289
BACnet License
Not Installed
Auto
Informational
290
Regen Low Temp
Check Furnace
Auto
Informational
291
Water Leak
Detected
Manual
Disable Compressors
292
Oil Level Switch
Inverter Compressor
Auto
Disable Inverter Circuit
293
Supply Water Temp 2
Sensor Value Not Valid
Auto
Disable Compressors
WSHP
294
Return Water Temp 2
Sensor Value Not Valid
Auto
Disable Compressors
WSHP
295 - 296 Low Suction SH ExV (x)
EVD Alarm
Auto
Disable Inverter Circuit
Only with EVD
297 - 298
LOP (x) EVD 1
Low Operating Pressure
Auto
Disable Inverter Circuit
Only with EVD
299 - 300
MOP (x) EVD 1
Max Operating Pressure
Manual
Disable Inverter Circuit
Only with EVD
301 - 302
EEV (x) EVD 1
Motor Alarm
Auto
Disable Inverter Circuit
Only with EVD
303 - 304
LowSuct (x) EVD 1
Refrigerant Temp
Auto
Disable Inverter Circuit
Only with EVD
305
High Condensing Temp
Auto
Disable Inverter Circuit
Only with EVD
306
Suction Press Sens S1
Sensor Value Not Valid
Auto
Disable Inverter Circuit
Only with EVD
307
Suction Temp Sens S2
Sensor Value Not Valid
Auto
Disable Inverter Circuit
Only with EVD
308
Probe S3 - Not Used
Sensor Value Not Valid
Auto
Disable Inverter Circuit
Only with EVD
309
Dschg Temp Sens S4
Sensor Value Not Valid
Auto
Disable Inverter Circuit
Only with EVD
310
EVD EEPROM Damaged
Call Unison
Auto
Disable Inverter Circuit
Only with EVD
311
Incomplete Closing EVD
Auto
Disable Inverter Circuit
Only with EVD
312
Emergency Closing EVD
Auto
Disable Inverter Circuit
Only with EVD
313
EVD Battery
Replace Battery
Auto
Disable Inverter Circuit
Only with EVD
314
FW Incompatibility
Call Unison
Auto
Disable Inverter Circuit
Only with EVD
315
EVD Config Error
Auto
Disable Inverter Circuit
Only with EVD
316
EVD Comm
EVD is Offline
Auto
Disable Inverter Circuit
Only with EVD
317
High Discharge Temp
Inverter Compressor Auto until Lockout 3x in 1 hr Disable Inverter Circuit Only with Inverter Scroll
318
Low Discharge Pressure
Inverter Compressor Auto until Lockout 3x in 1 hr Disable Inverter Circuit Only with Inverter Scroll
319
High Suction Pressure
Inverter Compressor Auto until Lockout 3x in 1 hr Disable Inverter Circuit Only with Inverter Scroll
CONTROLLER
Alarm Data