98
Rooftop Dedicated Outdoor
Air System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 57:
BACnet and MODBUS Points List, continued.
Variable
Description
Active
Text
Inactive
Text
BACnet
MODBUS
Object
Instance
Object
Type
Access
Hyst Index Register
Type Size
Binary Values – Read Only, continued.
Allow_Dampers
Startup sequence
command to open
dampers
Yes
No
43
BV
ReadCOV_NoWrite 0 10029 Discrete
Allow_Exhaust_Fans
Startup sequence
command to trigger
exhaust fans to start
Yes
No
44
BV
ReadCOV_NoWrite 0 10030 Discrete
Allow_Supply_Fans
Startup sequence
command to trigger
supply fans to start
Yes
No
48
BV
ReadCOV_NoWrite 0 10034 Discrete
BMS_Watchdog_Active
Status of the BMS
watchdog ping
Active
Inactive
49
BV
ReadCOV_NoWrite 0 10035 Discrete
BMS_Occupancy_Status
Status of the BMS
occupancy command Unoccupied Occupied
50
BV
ReadCOV_NoWrite 0 10036 Discrete
Cond_Water_Pump_
Required
WSHP Water Pump
Requested
On
Off
60
BV
ReadCOV_NoWrite 0 10042 Discrete
Damper_Actuator_Power_1_
Digital_Output
Damper Actuator
Power 1 Digital
Output
Active
Inactive
100
BV
ReadCOV_NoWrite 0 10153 Discrete
Compressor_1_Enable_
Digital_Output
Compressor 1 Enable
On
Off
111
BV
ReadCOV_NoWrite 0 10164 Discrete
Compressor_2_Enable_
Digital_Output
Compressor 2 Enable
On
Off
112
BV
ReadCOV_NoWrite 0 10165 Discrete
Compressor_3_Enable_
Digital_Output
Compressor 3 Enable
On
Off
113
BV
ReadCOV_NoWrite 0 10166 Discrete
Compressor_4_Enable_
Digital_Output
Compressor 4 Enable
On
Off
114
BV
ReadCOV_NoWrite 0 10167 Discrete
Condenser_Fan_1_Digital_
Output
Condenser Fan
Stage 1
On
Off
119
BV
ReadCOV_NoWrite 0 10172 Discrete
Condenser_Fan_2_Digital_
Output
Condenser Fan
Stage 2
On
Off
120
BV
ReadCOV_NoWrite 0 10173 Discrete
Condenser_Fan_3_Digital_
Output
Condenser Fan
Stage 3
On
Off
121
BV
ReadCOV_NoWrite 0 10174 Discrete
Exhaust_Fan_1_Start_Stop_
Digital_Output
Exhaust Fan 1 Start
Stop
On
Off
127
BV
ReadCOV_NoWrite 0 10180 Discrete
Furnace_1_Stage_1_Digital_
Output
Furnace 1 Stage 1
On
Off
131
BV
ReadCOV_NoWrite 0 10184 Discrete
Furnace_2_Stage_1_Digital_
Output
Furnace 2 Stage 1
On
Off
133
BV
ReadCOV_NoWrite 0 10186 Discrete
Heat_Wheel_Enable_Digital_
Output
Heat Wheel Enable
On
Off
163
BV
ReadCOV_NoWrite 0 10208 Discrete
PreHeat_Enable_Digial_
Output
PreHeat Enable
Digital Output
On
Off
166
BV
ReadCOV_NoWrite 0 10211 Discrete
Reversing_Valve_Digital_
Output
Reversing Valve
Heating
Cooling
175
BV
ReadCOV_NoWrite 0 10220 Discrete
Supply_Fan_1_Start_Stop_
Digital_Output
Supply Fan 1 Start
Start
Stop
186
BV
ReadCOV_NoWrite 0 10231 Discrete
Bacnet_License_not_
Installed_Alarm. Active
Bacnet License not
Installed Alarm
Alarm
Normal
300
BV
ReadCOV_NoWrite 0 10251 Discrete
BMS_Offline_Alarm.Active
BMS Offline Alarm
Alarm
Normal
313
BV
ReadCOV_NoWrite 0 10264 Discrete
Cold_Coil_1_Temperature_
Sensor_Alarm. Active
Cold Coil 1
Temperature Sensor
Alarm
Alarm
Normal
387
BV
ReadCOV_NoWrite 0 10338 Discrete
CONTROLLER
BACnet and MODBUS Points