Variable
Description
Ac-
tive
Text
Inactive
Text
BACnet
MODBUS
Object
Instance
Object
Type
Access
Hyst Index Register
Type Size
Binary Values – Read Only, continued.
Al_SuctHiP_COMP.Active
Compressor Envelope
- SuctHiP_COMP
Alarm Normal
618
BV
ReadCOV_NoWrite 0
10568 Discrete
Al_SuctLowP_COMP.Active
Compressor Envelope
- SuctLowP_COMP
Alarm Normal
619
BV
ReadCOV_NoWrite 0
10569 Discrete
High_Ent_Water_Temp_CircA.
Active
High Entering Water
Temp Alarm - Circuit A Alarm Normal
620
BV
ReadCOV_NoWrite 0
10570 Discrete
High_Ent_Water_Temp_CircB.
Active
High Entering Water
Temp Alarm - Circuit B Alarm Normal
621
BV
ReadCOV_NoWrite 0
10571 Discrete
Low_Ent_Water_Temp_CircA.
Active
Low Entering Water
Temp Alarm - Circuit A Alarm Normal
623
BV
ReadCOV_NoWrite 0
10573 Discrete
Low_Ent_Water_Temp_CircB.
Active
Low Entering Water
Temp Alarm - Circuit B Alarm Normal
624
BV
ReadCOV_NoWrite 0
10574 Discrete
Return_Water_Temp_2_Alarm.
Active
Return Water Temp 2
Alarm
Alarm Normal
626
BV
ReadCOV_NoWrite 0
10576 Discrete
Supply_Water_Temp_2_Alarm.
Active
Supply Water Temp 2
Alarm
Alarm Normal
627
BV
ReadCOV_NoWrite 0
10577 Discrete
Water_Leak_Detector_Alarm.
Active
Water Leak Detector
Alarm
Alarm Normal
628
BV
ReadCOV_NoWrite 0
10578 Discrete
HP_Defrost_Active.Active
Heat Pump Defrost
Alarm
Alarm Normal
631
BV
ReadCOV_NoWrite 0
10579 Discrete
Comp_Staging_Order_
Skipped.Active
Compressor Staging
Order is Skipped
Warning
Alarm Normal
632
BV
ReadCOV_NoWrite 0
10580 Discrete
Heat_Pump_Heating_Lock_
Out_Alarm. Active
Heat Pump Heating
Locked Out Alarm
Alarm Normal
633
BV
ReadCOV_NoWrite 0
10581 Discrete
EVD_PrePosition_Alarm.Active
Unexpected EEV
Position
Alarm Normal
634
BV
ReadCOV_NoWrite 0
10582 Discrete
Integer Values – Read Only
Allow_Fan_Delay_Remaining
Startup Sequence Fan
Damper Delay. Time
before enabling Fan
startup sequence.
1
IV
ReadCOV_NoWrite 1
30182
Input
2
Supply_Fan_Delay_Remaining
Supply Fan startup
sequence. Time before
starting supply fan.
2
IV
ReadCOV_NoWrite 1
30184
Input
2
Exhaust_Fan_Delay_
Remaining
Exhaust Fan startup
sequence. Time
before starting exhaust
fan.
3
IV
ReadCOV_NoWrite 1
30186
Input
2
LatestAlm
Most recent alarm. See
Alarm Table.
7
IV
ReadCOV_NoWrite 1
30194
Input
2
Table 61:
BACnet and MODBUS Points List, continued.
CONTROLLER
BACnet and MODBUS Points