Table 42: Network Settings Data Table, continued.
Control Variable
Default
Min.
Max.
Notes
USB Restore
Disable Unit Prior to Restore
Disabled
Disabled
Enabled
Enable Restore
No Restore (□) No Restore (□)
Restore (X)
Internal Restore
Disable Unit Prior to Restore
Disabled
Disabled
Enabled
Enable Restore
No Restore (□) No Restore (□)
Restore (X)
Last Save Time
hh: mm mm/dd/yy
IO Status/Offset
Input Offset Ch↑↓
Press Enter to select the analog input channel
Input Offset
Press Enter again to select a value to offset the input by
Input Offset Value
Current Value of the Channel selected
Channel Menu IO Type
Select the IO Type: Univ Ch, Digital In, Digital Out, Analog Out
Channel Menu Ch↑↓
Select the Channel: Dependent on control boards installed
Channel Menu Value
Current Value of the Channel selected
Unit Configuration
Exp 1
Not Installed
Not Installed, Standard c.pCO, c.pCOe
Exp 2
Not Installed
Not Installed, Standard c.pCO, c.pCOe
Exp 3
Not Installed
Not Installed, Standard c.pCO, c.pCOe
Expansion Connection Port
FBus2 to BMS2 FBus2 to BMS2
Ethernet IP
FB2 Expansion Board Baud Rate
19200
1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200
FB2 Expansion Board Stop_Bits
1
1
2
FB2 Expansion Board Parity
None
None, Odd, Even
Airflow Monitoring Density Calc
Disabled (□)
Disabled (□)
Enabled (X)
Supply Fan Control Type
Constant Volume Constant Volume, Duct Static, Space Static, Hardwired Input, Single
Zone VAV, CFM Control
Supply Fan Control K Factor
0.0
0.0
99999.9
Default determined
by the unit purchased
Exhaust Fan Control Type
Not Installed Not Installed, Constant Volume, Space Static, Sup Track w/Off, Pool
Space Static, CFM Control, Hardwired, Rtn Duct Static
Exhaust Fan Control K Factor
0.0
0.0
99999.9
Default determined
by the unit purchased
Dehumidification Mode Installed
Disabled (□)
Disabled (□)
Enabled (X)
Occupied Dehum. Call Enabled
Inside RH AND
Inside
Dewpoint OR
Outside
Dewpoint
Inside RH, Inside Dewpoint, Outside Dewpoint, Inside RH OR
Inside Dewpoint, Inside RH OR Inside Dewpoint OR Outside
Dewpoint, Inside RH AND Inside Dewpoint, Inside RH AND Inside
Dewpoint OR Outside Dewpoint
Unoccupied Dehum. Call Enabled
Inside RH
Inside RH, Inside Dewpoint, Inside RH OR Inside Dewpoint,
Inside RH AND Inside Dewpoint
Unoccupied Unit Operation
Night Setback
Cycle
Night Setback Cycle, Normal Op wUnoc Spts, Recirc wUnoc Spts
Morning Warm Up
CMN
Disabled (□)
Enabled (X)
Morning Cool Down
CMN
Disabled (□)
Enabled (X)
Max Duration
30 min.
0 min.
99 min.
Economizer Installed
CMN
Disabled (□)
Enabled (X)
Econ w/Mech Clg
Enabled (X)
Disabled (□)
Enabled (X)
CO
2
Control
CMN
Not Installed (□)
Installed (X)
OAD CFM Control
CMN
Not Installed (□)
Installed (X)
Min OAD CFM Control
CMN
Not Installed (□)
Installed (X)
Cooling Enabled
Enabled (X)
Disabled (□)
Enabled (X)
Set-point availability varies based on unit configuration.
CONTROLLER
Network Settings Data Tables