Table 38: Occupancy Set-Points Data Table.
Control Variable
Default
Min.
Max.
Notes
Occupancy Mode
BMS
BMS, Digital Input, Schedule, Always Occ,
Always Unocc
BMS Comm Loss Occupancy
Fallback Mode
BMS Last Known
BMS Last Known, Digital Input, Schedule,
Occupied, Unoccupied
Occupancy Schedule Day
Monday
Monday, Tuesday, Wednesday, Thursday, Friday,
Saturday, Sunday
All days on one screen.
Choose the day to change then the
operation and start / stop times
Mode
Occupied
Occupied, Unoccupied, Schedule
Start Time: 00:00
06:00 AM
12:00 AM
11:59 PM
Stop Time: 00:00
06:00 PM
12:00 AM
11:59 PM
Occupied Timed Override
Enable
Disabled (□)
Disabled (□)
Enabled (X)
Duration
60 min.
0 min.
240 min.
Occupied Auto Mode
Enable
Disabled (□)
Disabled (□)
Enabled (X)
Deadband
4.0 Δ°F
0.1 Δ°F
20.0 Δ°F
Unoccupied Start Enable Modes
Cooling
Enabled (X)
Disabled (□)
Enabled (X)
Heating
Enabled (X)
Disabled (□)
Enabled (X)
Dehumidification
Enabled (X)
Disabled (□)
Enabled (X)
CONTROLLER
Set-point availability varies based on unit configuration.
Set-Points Data Tables