90
Rooftop Dedicated Outdoor
Air System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 49: Alarm Data, continued.
Alarm ID Alarm Screen Line 1 Alarm Screen Line 2
Reset Type
Lockout
Action Type
Notes
320
Low Suction Pressure Inverter Compressor Auto until Lockout 3x in 1 hr Disable Inverter Circuit Only with Inverter Scroll
321
High Current
Inverter Compressor Auto until Lockout 3x in 1 hr Disable Inverter Circuit Only with Inverter Scroll
322
High Pressure Ratio
Inverter Compressor Auto until Lockout 3x in 1 hr Disable Inverter Circuit Only with Inverter Scroll
323
Low Pressure Ratio
Inverter Compressor Auto until Lockout 3x in 1 hr Disable Inverter Circuit Only with Inverter Scroll
324
Low Delta P
Inverter Compressor Auto until Lockout 3x in 1 hr Disable Inverter Circuit Only with Inverter Scroll
325
High Discharge Press Inverter Compressor Auto until Lockout 3x in 1 hr Disable Inverter Circuit Only with Inverter Scroll
326 -327
WSHP Freeze
Protection Circuit (x)
Auto
Disable Compressors
328 - 329
Low Entering Water
Temp - Circuit (x)
Auto
Informational
330 - 331
High Entering Water
Temp - Circuit (x)
Auto
Informational
332
Compressor Staging
Order Skipped
Auto
Informational
333
HP Defrost 3 Strike
HP Heating Not Avail
Manual
Disable HP Heating
2 hours + Temp Rise for
Reset
334
EVD Error
Unexpected Position
Auto
CONTROLLER
Alarm Data